SGM LEKTRA MTU5 Quick Start Manual

Ultrasonic level transmitter

Advertisement

Quick Links

Technical Data
Housing material:
Mechanical installation: DN150 PP fl ange or bracket
Protection degree:
Electrical connection:
Working temperature: -30 ÷ +70°C; +80°C non-continuous
Pressure:
Power supply: 24Vdc or 24, 115, 230Vac (specify at the order)
Power consumption:
Analog output:
Relays output:
Digital communication:
Max measure range:
[In case of non perfectly refl ecting surfaces, the maximu
distance value will be reduced]
Blind distance:
Temperature compensation:
Accuracy:
±0,5% (of the measured distance)
Resolution:
Calibration:
Warm-up:
LCD Display: Plug-in display/keyboard 4 buttons matrix LCD
Warranty
Products supplied by SGM LEKTRA are guaranteed for a period of 12 (twelve) months from delivery date according to
the conditions specifi ed in our sale conditions document.
SGM LEKTRA can choose to repair or replace the Product.
If the Product is repaired it will mantein the original term of guarantee, whereas if the Product is replaced it will have 12
(twelve) months of guarantee.
The warranty will be null if the Client modifi es, repair or uses the Products for other purposes than the normal conditions
foreseen by instructions or Contract.
In no circumstances shall SGM LEKTRA be liable for direct, indirect or consequiential or other loss or damage whether
caused by negligence on the part of the company or its employees or otherwise howsoever arising out of defective goods
Factory Test Certifi cate
In conformity to the company and check procedures I certify that the equipment:
MTU5
...................................... Production and check date:
Serial n. .......................................................
is conform to the technical requirements on Technical Data and it is made in conformity to the SGM-LEKTRA procedure
Quality Control Manager
Ultrasonic level transmitter
PC / PP wetted part
IP67 / IP68 (sensor)
Internal push connectors
from 0,5 to 1,5 bar (absolute)
max 1,5W
4÷20mA, max 750ohm
n°2 3A 230Vac (n.o.)
MODBUS RTU
max 0.5÷12m
digital from -30 to 80°C
not better than ±3mm
4 buttons or by MODBUS RTU
5 minutes typical
.................................
Process Control and Measurement
MTU5
0,5m
1mm
................................
825B136A

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MTU5 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for SGM LEKTRA MTU5

  • Page 1 LCD Display: Plug-in display/keyboard 4 buttons matrix LCD Warranty Products supplied by SGM LEKTRA are guaranteed for a period of 12 (twelve) months from delivery date according to the conditions specifi ed in our sale conditions document. SGM LEKTRA can choose to repair or replace the Product.
  • Page 2: Installation Precaution

    SGM-LEKTRA developed the MTU5 unity to best meet the “GENERAL-PURPOSE” application requests. The MTU5 unit offers, together with its compact size, a complete versions range that makes the MTU5 very versatile for the most varied applications, including areas with explosion hazard and chemically aggressive environments. MTU5 is an ultrasonic level transmitter, temperature-compensated and suitable for connection with MODBUS RTU acquisition systems.
  • Page 3: Mounting Examples

    MTU5 - Mechanical installation 122mm Drilling template 37.5mm view Fig.3 75mm 2.2 Mounting examples Fig.4 Fig.5 2.3 Mounting precautions 2.3.1 Mounting position (Fig.6) Fig.6 - With cambered roof, Do not install the sensor in the tank center (b). Leave a 500mm minimum distance between the sensor and the tank smooth wall (d).
  • Page 4: Mechanical Installation

    2.3.5 Agitators presence The level measurement is possible thanks to the Auto-Tuned statistical fi lter. Should rarely need to adjust the fi lter setting by editing 2 MTU5 sensor programming parameters: - FILTER; this parameter is present in the Quick Setup menu (page 9) and in the Advanced Confi...
  • Page 5: Configuration Modes

    - read on your PC monitor all measures in reading and MTU5 operation data - programming all MTU5 confi guration parameters - storing on fi les, data logger function; MTU5 measures in reading and operating states Page 5 of 28...
  • Page 6 4.3 via VL601 confi guration The VL601 programming module can be mounted and removed from the MTU5 without affecting the unit operation. Unscrewing the cap, the VL601 module can be mounted (by clockwise rotation until it clicks) or dismounted (by rotation counterclockwise) as shown in Fig.14.
  • Page 7 The menu structure is represented on page 8 and on pages 13÷14. Fig.15 With the VL601 module is possible to access two confi guration modes for the MTU5 setting: QUICK START - Menu with easy access for quick basic parameters confi guration.
  • Page 8: Quick Start Mode

    MTU5 - Quick Start 5. QUICK START MODE From “RUN” mode press to access the Quick Setup menu Select the parameters by moving the cursor with and confi rm with press to exit 5.1 Quick Setup menu structure Page 8 of 28...
  • Page 9 MTU5 - Quick Start 5.2.1 SET DISTANCE 4mA Press to display the distance value associated MTU5 with 4mA output. reference point t t t t to modify that value; in the Fig.16 example, 20mA distance the 4mA distance is 3500mm.
  • Page 10 When confi rming with the button the maximum level threshold value storage, in the example 700m (fi gures 20 and 21), the MTU5 activates RL1 with the following default settings for level alarm threshold: 1) MIN / MAX = MAX; maximum level alarm 2) DELAY = 0 sec.;...
  • Page 11 When confi rming with the button the maximum level threshold value storage, in the example 3000mm (fi gures 22 and 23), the MTU5 activates RL2 with the following default settings for level alarm threshold: 1) MIN / MAX = MIN; minimum level alarm 2) DELAY = 0 sec.;...
  • Page 12: Quick Start

    Fig.24 5.2 ECHO MAP Pressing the BK, from RUN mode, to access directly to the echoes digital map display, which are in MTU5 receiving (Fig.25). This function is useful for: - properly orient the transducer pointing. - verify the echoes in acquisition correctness.