SGM LEKTRA TC26 Quick Start Manual

Compact capacitance level transmitter with settable relay built-in

Advertisement

Quick Links

Compact capacitance level transmitter with settable relay built-in

Technical Data

Enclosure material:

Mechanical installation:

(to be insert into IP65 enclosure)
Mechanical protection:
Electrical connection:
Working temperature:
Power supply depend to the model:
Power consumption:
Analog output:
Relays output:
Serial port:
Measure range:
Temperature compensation:
Linearity:
Calibration:
two push-buttons, for self-acquisition
LEDs display:
TC26-9
LEVEL 4-20mA transmitter + 1 settable relay insert, digital
tecnology, termal-drift compensation, two pushbuttons or
RS485 port for calibration. Local or remote calibration
possibility.
fig.1
fig.2
TC26/27/28/29
PP+Carbon steel
2 x 6pole plug-in connectors
-30 to +80°C
TC26 24Vdc, TC27 24Vac,
TC28 115Vac, TC29 230Vac
max 2,5W (1,5W Vdc)
4÷20mA max load 500 ohm
1 x SPDT 2A, 230Vac (resistive)
20pF÷10.000pF
by ref. internal capacitor
green LED flashing=measure
Fix=calibration
yellow LEDs for rel1 action
General
applied solutions for the applications
Bajonet
IP50
RS485
0,5%
TC26-9
The TC26-9 insert must be lodge into the IP65 capacitance-
sensor head commection.
Important to screw tight the cover of the head connection and
the cable gland in order to grant the sensor IP65.
Thanks to the bajonet fixing-system, to insert or remove the
TC26-9 from the head connection need to push and rotate.
Rotate clock-wise to fix into the head
Rotate reverse-clock-wise to remove from the head
fig.3
Mechanical installation
825B030D

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TC26 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for SGM LEKTRA TC26

  • Page 1 TC26-9 Mechanical installation fig.1 The TC26-9 insert must be lodge into the IP65 capacitance- sensor head commection. Important to screw tight the cover of the head connection and the cable gland in order to grant the sensor IP65. Thanks to the bajonet fixing-system, to insert or remove the TC26-9 from the head connection need to push and rotate.
  • Page 2 TC26-9 Setpoint Calibration The TC26-9 relay(RL1) operates as max level alarm (threshold1). This configuration is the default factory configuration and it can be changed by means RS485 port and the TC S/W communication. To calibrate the threshold1 of maximum levelneeds to move the level at the threshold point than: press simultaneously P1 and P2, release them and verify that “Mode led”...
  • Page 3 With PC or PLC soft. communication with RS485 port. To calibrate by-means 2 push-buttons P1 and P2 (see figure), needs to lodge the “TC26-29” into the head connection of the capacitance sensor and to install into the vessel or tank to be measured.
  • Page 4 If only a limitate level variation is possible, the calibration of the TC26-9 is still possible. Need to connect a current-meter on the TC26-9 output current and verify the present level point at which make the calibration. Supposely you are on the Low-point calibration, and the relevant level is 26%(8,16mA) than;...

This manual is also suitable for:

Tc27Tc28Tc29

Table of Contents