Clearances To Combustibles; Leveling Leg Adjustment; Thermostat Installation - HAMPTON BAY Greenfire GC60-2 Technical Manual

Freestanding cast iron pellet stove
Hide thumbs Also See for Greenfire GC60-2:
Table of Contents

Advertisement

c
c
learanceS to
ombuStibleS
Back Wall
3"
(76mm)
9"
(229mm)
Figure 4: GC60-2 Clearance to Combustibles
l
l
a
eveling
eg
djuStment
The leveling legs should be adjusted for the unit to to sit level and not rock if installed on uneven flooring.
1. Turn levelling legs until they are at the required heights.
2. Tighten the nut to hold the leveling leg in position.
t
i
hermoStat
nStallation
Remove jumper
wire and install
thermostat wires here.
Figure 5: Thermostat wire placement
10
Installation
:
3"
(76mm)
:
:
1. Install the wall thermostat (millivolt rated thermostat
2. Connect the Thermostat using a 2 x 18 gauge wire
If the heat in the room becomes to great, the high limit
switch may turn the stove off and the switch will have to
be manually reset. The switch is found below the firebox
top on the hopper's right surface.
These dimensions are minimum clearances but it
is recommended that you ensure sufficient room
for servicing, routine cleaning and maintenance.
Side wall to unit
Back wall to unit
Corner to unit
Ceiling height
Alcove Maximum Depth 36 inches (914 mm)
Alcove Minimum Width
Alcove Minimum Height 60 inches (1524 mm)
In the USA, the unit must be installed with a
minimum of 6" (152 mm) of floor protection in
front of and to the sides of the door opening.
In Canada, the unit must be installed with a
minimum of 8" (203 mm) of floor protection in
front of and to the sides of the door opening.
recommended, or a 12/24 Volt rated thermostat set to
millivolts) in a location that is not to close too the unit
but will effectively heat the desired area.
from the unit to the thermostat.
Hampton GC60-2 Cast Pellet Stove Technical Manual
9 inches
(229 mm)
3 inches
(76 mm)
3 inches
(76 mm)
60 inches
(152 mm)
48 inches (1219 mm)