3.3 Lubrication System

3.3.1

Oil Specifications

Use oil that meets the American Petroleum Institute
(API) classification of SC, SD, SE, SF, SG, or SH. Using
unsuitable oil or neglecting an oil change may result in
engine damage that is not covered by the engine
warranty. Figure 3-1 shows the recommended Society
of Automotive Engineers (SAE) viscosity designation for
given operating temperature ranges.
Do not mix different oil brands. Incompatibility could
cause a breakdown of lubricating ingredients and
reduce engine protection.
Recommended SAE Viscosity Grades
SAE10W-30/SAE 10W-40*
SAE5W-20*
°F -4
32
14
°C -20
0
-10
* Using multigrade oil causes greater oil consumption.
Figure 3-1 Engine Oil Selection
3.3.2

Oil Check

Check the oil level in the crankcase daily or before each
start-up to ensure that the level is in the safe range. Do
not check the oil level while operating the unit. Stop the
generator set and keep the generator set level to get an
accurate reading. To check the oil level, remove the
dipstick and wipe the end clean, reinsert and remove.
Maintain the oil level between the Full and Add marks on
the
dipstick,
as
shown
Section 1—Service Views for the dipstick location.
10
Section 3 Scheduled Maintenance
SAE40
SAE30
50
68
86
104
10
20
30
40
in
Figure 3-2.
See
1. Full mark
2. Add mark
Figure 3-2 Oil Level Check
Note: Do not operate the set if the oil level is below the
Add mark on the dipstick or above the Full mark
on the dipstick.
3.3.3

Oil Additions

Adding some oil between oil changes is normal. The
amount varies with generator set usage. Open the oil fill
cap and pour in a small amount of oil using a funnel or
other suitable pouring device. See Section 1—Service
Views for the oil check and oil fill locations.
3.3.4

Oil Change

Change the oil according to the service schedule or
before generator set storage. Change the oil more
frequently if the generator set operates under dirty,
dusty conditions. Change the oil while the engine is still
warm.
See Figure 3-3 for oil capacity.
Section 1—Service Views for oil fill, oil check, and oil
filter locations.
Model
All models
Figure 3-3 Oil Capacity (with Filter)
1
2
TP-5586-3
See
L (Qts.)
1.36 (1.44)
TP-5985 10/02