Installation
1
1
2
INFO
LAN cable requirements:
CAT7
Max. 100 m
4.
Connect Ethernet cable to one of the LAN sockets in the COM2 connection panel.
The second LAN socket is used to continue the network connection to further invert-
ers.
5.
Mount COM2 cover cap.
Torque: 1.5 Nm
6.
Connect the other end of the Ethernet cable to the router.
7.
Establish a LAN connection from the KOSTAL Smart Energy Meter to the router.
8.
In this variant, the KOSTAL Smart Energy Meter works as a slave and sends data to
the inverter.
9.
In the KOSTAL Smart Energy Meter, set Modbus settings > Modbus TCP > Slave
(Enable TCP Slave) to ON.
10.
To make the home consumption visible in the KOSTAL Solar Portal, in the KOSTAL
Smart Energy Meter set Inverter > Solar portal > Activate solar portal to ON.
After commissioning, the following settings still have to be configured in the KOSTAL PIKO
CI app.
1.
The use and installation position of the KOSTAL Smart Energy Meter (KSEM) must be
set in the KOSTAL PIKO CI app on the Master inverter.
This can be set under Settings > Inverter settings > Power adaptation/controls >
Energy management > Power limitation function > KSEM and Settings > Inverter
settings > Power adaptation/controls > Energy management > Sensor position
> Grid connection point (default value).
© 2022 KOSTAL Solar Electric GmbH
3
4
5
6
7
8
9
10
56