Interface Overview - Carrier WeatherMaker 50FCQ 04 Series Installation Instructions Manual

Single package rooftop heat pump with puron (r-410a) refrigerant
Table of Contents

Advertisement

Table 7 — HH57AC081 Sensor Wiring Terminations
TERMINAL
NUMBER
LABEL
1
S-BUS
2
S-BUS
Use Fig. 49 and Table 8 to set the DIP switches for the desired use
of the sensor.
Table 8 — HH57AC081 Sensor DIP Switch
DIP SWITCH POSITIONS FOR SWITCHES 1, 2, AND 3
USE
1
DA
OFF
RA
ON
OA
OFF
NOTE: When an S-Bus sensor is connected to an existing net-
work, it will take 60 minutes for the network to recognize and
auto-configure itself to use the new sensor.
During the 60 minute setup period, no alarms for sensor failures
(except SAT) will be issued and no economizing function will be
available.
CO
Sensor Wiring
2
When using a CO
sensor, the black and brown common wires are
2
internally connected and only one is connected to "IAQ COM" on
the W7220. Use the power from the W7220 to power the CO
sensor OR make sure the ground for the power supplies are com-
mon. See Fig. 50 for CO
sensor wiring.
2
CO
SENSOR
2
24V
+
ANALOG
OUT
1
POWER SUPPLY. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
Fig. 50 — CO

INTERFACE OVERVIEW

This section describes how to use the EconoMi$er
interface for:
Keypad and menu navigation
Settings and parameter changes
Menu structure and selection
User Interface
The user interface consists of a 2-line LCD display and a 4-button
keypad on the front of the economizer controller.
Keypad
Use the four navigation buttons (see Fig. 51) to scroll through the
menus and menu items, select menu items, and to change parame-
ter and configuration settings.
TYPE
DESCRIPTION
S-BUS
Communications
S-BUS
(Enthalpy Control
Sensor Bus)
S-BUS
Communications
S-BUS
(Enthalpy Control
Sensor Bus)
2
3
ON
OFF
OFF
OFF
OFF
OFF
RED
L1
(HOT)
BLACK
L2
1
YELLOW
BROWN
ORANGE
GREEN
Sensor Wiring
2
®
To use the keypad when working with menus:
Press the ▲ (Up arrow) button to move to the previous
menu.
Press the ▼ (Down arrow) button to move to the next
menu.
Press the
currently displayed menu.
Press the
and return to the list of menus.
Fig. 51 — W7220 Controller Navigation Buttons
To use the keypad when working with Setpoints, System and Ad-
vanced Settings, Checkout tests and Alarms:
1.
Navigate to the desired menu.
2.
Press the
2
currently displayed menu.
3.
Use the ▲ and ▼ buttons to scroll to the desired parameter.
4.
Press the
rently displayed item.
5.
Press the ▲ button to increase (change) the displayed param-
eter value.
6.
Press the ▼ button to decrease (change) the displayed param-
eter value.
NOTE: When values are displayed, pressing and holding the
▲ or ▼ button causes the display to automatically increment or
decrement.
1.
Press the
store it in nonvolatile RAM. "CHANGE STORED" displays.
2.
Press the
parameter.
3.
Press the
X user
menu.
Menu Structure
Table 9 illustrates the complete hierarchy of menus and parame-
ters for the EconoMi$er
The Menus in display order are:
STATUS
SETPOINTS
SYSTEM SETUP
ADVANCED SETUP
CHECKOUT
ALARMS
NOTE: Some parameters in the menus use the letters MA or
MAT, indicating a mixed air temperature sensor location before
33
(Enter) button to display the first item in the
(Menu Up/Exit) button to exit a menu's item
(Enter) button to display the first item in the
(Enter) button to display the value of the cur-
(Enter) button to accept the displayed value and
(Enter) button to return to the current menu
(Menu Up/Exit) button to return to the previous
X system.
®

Advertisement

Table of Contents
loading

Table of Contents