Content General Description Function Matching capacity of hot water boiler and SWH Guarantee Technical Technical data Dimensions Operating parameters Pre-check Installation Suspension Water connections Electrical connection 230Vac Supply General functioning of the unit Connecting options 4.3.1 Connection with only a room thermostat 4.3.2 Connection with room thermostat combined with contact thermostat...
In case the capacity of the boiler is higher than that of exchanger consist of copper tubes and aluminium fins. the SWH, the boiler won’t be able to release all the heat This is an approved design for an optimal heat exchange.
3. Installation Working pressure: Max. 5 bar 3.1 Suspension Water temperature: Max. 100⁰C The SWH is provided with 8 No M10 suspension points Min. 4⁰C (risk of freezing) on the side panels. Ambient temperature: Max. 40⁰C Min. 4⁰C (risk of freezing)
4.2 General functioning of the unit The SWH is simply described as a radiator with a fan at the rear. If there is hot water flowing through the radiator, and the heater is on, the heater will blow warm air.
(disconnect) causing the SWH fan to stop. The on/off room thermostat will operate the fan of the SWH when there is a demand for heat. The fan will blow air over the heat exchanger, if the water is hot the heater will discharge warm air.
Contact thermostat vacuum cleaner or compressed air taking care to avoid- will supply power to the SWH. The fan will op- void damaging the heat exchanger fins. erate. If an optional 5 speed switch has been Clean also the fan, guard and air outlet grille.
6.1 Example What is the output of a SWH 230 with a water supply temperature of 80/60 °C, with an air temperature of 10°C with the 5 speed switch is set to 3? Look in the SWH 230 performance sheet, select 80/60°C water temp and the row for air temp 10°C.