SSA81U Electronic Valve Actuator
24 Vac Floating Control
Operation
Mounting and
Installation
Wiring
Siemens Industry, Inc.
The actuators can be driven manually to any position between 0 and 1 with a 3 mm hex
wrench. The control signal from the controller; however, will take priority over any
manual position.
Mount the actuator in one of the allowable positions shown in Figure 3.
NOTE:
Vertical is the recommended position.
When mounting the actuator in a plenum, the proper cable must be attached to meet
local codes.
Allow 8-inches (200 mm) above the actuator and 8-inches (200 mm) behind the cable
for service.
Installation Instructions are included with the actuator.
•
Do not use autotransformers.
•
Use earth-ground isolating, step-down, Class 2, power supplies.
•
Determine supply transformer rating by summing total VA of all actuators used.
•
Use one transformer to power up to 10 actuators.
Figure 3. Mounting Position.
Figure 4. SSA81U Wiring Diagram.