Controller Installation - LG MULTI V ARNH423K3A4 Installation Manual

Hydro kit high temperature (k3)
Table of Contents

Advertisement

Hydro Kit Wired Remote Controller Installation
(Included with the Hydro Kit)
• Always have power off before installing the controller.
Never operate Hydro Kit outside of the operational parameters as outlined in this manual and the product specifications.
Never touch wiring or install accessories with wet hands.
• When drilling holes for the communication cable and the screws, take care not to damage wiring that is routed through the wall.
• See the Installation section for guidelines on where to place the controller.
• The controller is designed to be surface mounted. Recessing the controller will damage the temperature sensor, and cause it to misread the
zone temperature.
1. If not already done, separate the Hydro Kit controller from its
installation plate.
• To separate, insert a small screwdriver into one of the two holes at
the bottom of the installation plate. Gently turn clockwise.
• Repeat for the remaining hole, and then gently pull outward on the
bottom of the controller body.
Do not damage the controller components when separating. There
components are damaged.
2. Determine how the Hydro Kit communications cable (female end)
will be routed to the controller. Choose either through the back,
using the top groove, or using right groove.
• If using the top or right groove, use needle nose pliers to carefully
break off the tab.
• If using the back, route the communications cable through the
handy box or wall, and through the large hole in the installation
plate.
• If the distance between the controller and the Hydro Kit is more
rately).
Do not install a cable longer than 164 feet (50 m). Communica-
tion errors will occur.
• Ensure the cable connections are male to female. If the communi-
cations cable is not routed properly with the connections facing the
right direction, connections cannot be made.
3. Attach the controller installation plate to the wall or handy box using the factory-provided screws. Ensure the plate is level and securely
attached to the wall.

CONTROLLER INSTALLATION

-
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
Figure 66: Removing the Controller from the Installation Plate.
Figure 67: Routing the Communications Cable.
Top Cable Groove
Right Cable
Groove
Handy Box
Access
Figure 68: Location of the Controller Installation Plate Screws When
Using a Handy Box.
Four-Socket Handy Box Installation
Top Cable Groove
Right Cable
Groove
Two-Socket Handy Box Installation
71