LG MULTI V ARNH423K3A4 Installation Manual page 108

Hydro kit high temperature (k3)
Table of Contents

Advertisement

INSTALLATION CHECKLIST
Hydro Kit Wall Mounted Controller Communications
LG factory provided Hydro Kit Wall Mounted Controller stranded, shielded (white jacket) cable was used
between the Hydro Kit Wall Mounted Controller(s) and the Hydro Kit(s).
Hydro Kit Wall Mounted Controller cable has NOT been cut, spliced, or tied together with wire caps. Fac-
tory plugs are present.
Cable is securely plugged into the socket on the Hydro Kit Wall Mounted Controller or the three screw
Hydro Kit Control Panel
Hydro Kit Wall Mounted Controller cable is securely plugged into the CN-REMO socket on the Hydro Kit
main PCB.
If an optional remote temperature sensor was installed, the associated cable is plugged into socket CN-
ROOM.
Hydro Kit unit DIP switches have been adjusted for application (group control-master/slave; water heating
only, etc.)
Wiring harness "Plug C" has been properly connected to either "Plug A" or "Plug B" based on the type of
thermostat and/or room sensor was installed.
All wiring harness connections have been checked and are securely connected to the plug sockets.
Power and communications cables are properly restrained and separated.
108
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
PAGE 2