TH On / Off Variable, Heating Air
Setting thermal on / off air temperature difference for heating mode.
Table 35: TH On / Off Variable, Heating Air Settings.
Setting
0
-9°F (-0.5°C)
1
-1.8°F (-1°C)
2
-3.6°F (-2°C)
3
-5.4°F (-3°C)
TH On / Off Variable, Domestic Hot
Water
Setting thermal on / off domestic hot water temperature difference
for heating mode.
Table 37: TH Variable, DHW Settings.
Setting
0
-3.6°F (-2°C)
1
-10.8°F (-6°C)
2
3.6°F (-2°C)
3
-1.8°F (-1°C)
Heating Temperature Setting
Sets the water pipe temperature control standard for heating in accordance with the field environment.
Pump Setting in Heating
Sets the water pump operation / delay time option for heating. This function helps the mechanical life of the water pump by life by incorporat-
ing down time in the system (pump is not operating or is delayed in operating).
Forced Operation (Water Pump)
If the water has not been circulating in the Hydro Kit water circuit for 20 to 180 hours (default: 20 hours), this function will switch ON the
pump and force the water to circulate for 1 to 10 minutes (default: 10 minutes). Forced Operation function can be used to prevent the water
in the circuit from freezing, etc.
TH On
TH Off
2.7°F (1.5°C)
3.6°F (2°C)
5.4°F (3°C)
7.2°F (4°C)
TH On
TH Off
3.6°F (2°C)
7.2°F (4°C)
7.2°F (4°C)
1.8°F (1°C)
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp.
TH On / Off Variable, Heating Water
Setting thermal on / off water temperature difference for heating
mode.
Table 36: TH On / Off Variable, Heating Water Settings.
Setting
0
-3.6°F (-2°C)
1
-5.4°F (-3°C)
2
-7.2°F (-4°C)
3
-1.8°F (-1°C)
PRE-STARTUP
Functions
TH On
TH Off
3.6°F (2°C)
5.4°F (3°C)
7.2°F (4°C)
1.8°F (1°C)