2.3

Factory integrated components

Burner integration kit installed and tested.
► 4.3" HMI (LMV3/LMV5)
► 7.0" HMI (LMV5)
Protocol gateway (optional)
2.4
Standard features
In order to handle a wide variety of systems, the touch-
screen is configurable. Please note that most of these
features will not appear in certain modes. The following
option are available:
System output type:
► Steam
► Hot water
Monitoring of burner/boiler & system:
► PV, statuses, firing rate, communication
Setpoint selection:
► Local (selectable/night/weekend setpoint)
► BMS (network/hardwire via analog signal 4-20ma or
0-10Vdc) - note this is not available for Solo or Piccolo LMV5
Night/weekend setback
► Individual days selection
► Individual time and setpoint selection
Hot Standby
► Selectable temperature/pressure target
► Choice of first lag boiler or all lag boilers
Cold start
► Individual start and stop of setpoint selection
► Maximum time selection
0214190 - 01/2022
System and hardware configuration
6
Pumps setup
► Boiler circulator pump off delay
► Boiler isolation valve closed delay
Modbus RTU connection for BMS connection to software
points.
Modbus TCP connection for BMS in Solo mode
Remote viewing
Piccolo
► Start and stop for lag boiler
► Start and stop delay for lag boiler
► Boiler automatic setpoint correction function
► Lead boiler rotation interval
Massimo: Touchscreens configurable to work in conjunction
with Massimo Panel