3.3

Burner Mode

Standalone (Solo): The burner will use local or remote
setpoint to modulate and maintain the process value (PV),
without any external intervention. When the selected media
is steam and hot standby is active, sending a setpoint of
0 PSI will shut down the burner, however the boiler will be
kept warm within the limits of the hot standby routine.
Manual ON: starts the burner and runs at the specified
manual load for an undetermined period of time. The
temperature or pressure limit control will still shut down the
system.
Manual OFF: stops the burner for an undetermined period
of time regardless any existing call for heat.
3.4
System Configuration (main menu)
Refer to 3.5
Refer to 3.6
Refer to 3.7
Refer to 3.15
Navigation buttons to all func-
tion configuration pages are
locating in "System Configura-
tion".
0214190 - 01/2022
User interface
Remote Modulation: The burner will run at the specified
load received from the BMS system. Load requests from the
BMS with value below 20% will shut down the burner.
Lead/Lag Piccolo mode: enables communication and
control for the 2 boiler Lead/Lag system (refer to section 3
Piccolo user manual).
Lead/Lag Massimo mode: enables communication and
control for the 2+ boiler Lead/Lag system (refer to section 4
Massimo user manual).
Refer to 3.10
Refer to 3.8
Refer to 3.9
Refer to 3.7
Refer to 3.8
Refer to 3.2
14
Solo
Piccolo
Refer to 3.11
Refer to 3.16
Massimo
Refer to 3.12
Refer to 3.13
Refer to 3.14