Lighting panelboards - branch circuit monitoring

Advertisement

ASPMETER split core
3. Connect adapter boards to the main board using ribbon
cable (Figure 8). Ribbon cables are keyed to ensure proper
installation.
Orient cables so that the red stripe is on the left.
NOTE: Flat and round ribbon cables are available.
See recommended accessories.
4. Connect current sensors to the terminals on the adapter
boards (Figure 8).
Figure 8.
Red Stripe
Red Stripe
Red stripe
Red Stripe
Red Stripe
Align ribbon cable key with connector keyhole.
Orient ribbon cable so that the red stripe is on
the left side of the connector.
Panel 1
If the signed power factor feature is NOT enabled, the current sensor orientation does
not affect meter behavior. If this feature IS enabled, orient the current sensors so that
the arrow points toward the load for proper operation.
A S P M E T E R S P L I T C O R E
A
Panel 1
Panel 2
A
B
Panel 1
Panel 2
B
A
A
Panel 1
Panel 1
Panel 2
Panel 2
B
B
5. Install the current sensors onto the conductors to be
±
I1
monitored (Figure 9). Sensors can be mounted facing
±
I2
either direction; orientation does not affect meter
±
I3
accuracy.
±
IN
Note: Clean split-core contacts before closing. The hinge
can detach, allowing the base and the top to separate for
easier cleaning and installation.
Figure 9.
The 50 A CT accepts a maximum #2 AWG (0.384" O.D.) wire with THHN insulation.
V1
The 100 A CT accepts a maximum 3/0 AWG (0.584" O.D.) wire with THHN insulation.
The 200 A CT accepts a maximum of 350 MCM wire with THHN insulation. Use this
gauge wire or smaller for each circuit.
A
A
B
L - L
B
A
A
B
B
6. Plastic cable ties are included with the product for strain
relief. Insert the strain relief device into one of the available
holes on the adapter board (Figure 10A). Gather all current
sensor wires connected to that adapter board and secure
the cable tie around them (Figure 10B).
Figure 10A.
Figure 10B.
V2
V3
N
Close CTs until the clasp clicks into place
L - N
to ensure that contact surfaces are firmly
seated.