Examination / Maintenance - D+H RZN 4402-K V2 Original Instructions Manual

Hide thumbs Also See for RZN 4402-K V2:
Table of Contents

Advertisement

Available languages

Available languages

Examination
Every six months and after repair by a specialist or staff, who has been introduced to the task.
Eliminate shortcomings immediately. Keep log book.
Preparation:
- Notify user, that the system is out of operation.
- Notify user about false alarms.
- Interrupt or switch-off monitored alarm indication
and remote controls.
Inspection:
- Check all appliances and cable connections for
outer damage and dirt accumulation.
- Fire detectors, smoke vent buttons, smoke vents
and so on must not be impaired in their function
by goods in storage or structural changings.
Smoke vent buttons:
- Open smoke vent button.
- Press red alarm button
- Red LEDs lightens in buttons and control panel.
- Smoke vent must open.
- Press button
shortly
- Red LEDs extinguishes in buttons and control
panel.
- If DIP switch 5 = ON: Smoke vent must close.
- If DIP switch 5 = OFF: Press button
until the smoke vent is closed.
Maintenance
Once a year by a specialist company, who is
authorized by the appliance manufacturer.
Renew test badge, keep log book.
The respective current D+H maintenance
instruction is decisive.
D+H authorized expert companies have been
specially trained by D+H for carrying out expertly
this maintenance, and they get automatically the
latest maintenance instructions.
30/32
RZN 4402-K / RZN 4404-K
(~1 sec.).
again,
Automatic fire detectors / External control:
At severe dirt accumulation visible from outside or
false alarms, send detector in for maintenance and
install an exchange detector.
- Release smoke detector individual by smoke
detector tester, as an alternative by cigarette
smoke (response delay circa 20 sec.)
release external control.
- Red LEDs in the buttons, in control panel and
where appropriate at the fire detector must light.
- Smoke vent must open.
- Wait until there is no more smoke in detector
open contact in external system for closing, for
example by resetting of fire detector system.
- Reset line in control panel (switch off/ switch on
press button). The line can also be directly reset
via smoke vent button, if Dip switch 9 = OFF.
For this, press button
- Red LEDs extinguishes.
- If DIP switch 5 = ON: Smoke vent must close.
- If DIP switch 5 = OFF: Press button
until the smoke vent is closed.
Emergency supply:
- Detach fuse MAINS in the distribution box
- Green LED
- Repeat functioning testing.
- Green
in smoke vent buttons must not light.
OK
- Ventilation function is inoperative.
- If DIP switch 4 and 5 = ON: The group will be
automatically closing.
Following tests must be carried out in the course of
maintenance:
- Outside examination / inspection of system
components
- Measuring of insulation resistances
- Checking of all relevant power supply units
- Functional testing of connected system
components
- Record of competent carrying-out of
maintenance, and designation according
to directions
English
shortly (~1 sec.).
on control panel must not light.
99.823.80 2.1/08/12
or
or
again,

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rzn 4404-k v2

Table of Contents