RZN 4404-K V2
Original instructions
RZN 4404-K V2
(ZP RZN 4404-K V2 + GEH-KST)
0786 - CPD - 50383
EN 12101-10 : 2005/AC:2007
conform
RZN 4404-KS V2
(ZP RZN 4404-K V2 + GEH-S-RWA)

Advertisement

Table of Contents
loading

Summary of Contents for D+H RZN 4404-K V2

  • Page 1 RZN 4404-K V2 Original instructions RZN 4404-K V2 RZN 4404-KS V2 (ZP RZN 4404-K V2 + GEH-KST) (ZP RZN 4404-K V2 + GEH-S-RWA) 0786 - CPD - 50383 EN 12101-10 : 2005/AC:2007 conform...
  • Page 2: Table Of Contents

    Mounting of SHEV control panel with housing GEH-KST................6 View motherboard............................7 DIP switch settings .............................8 Cables for D+H smoke an heat vent systems / Wiring plan (Paragon) ............9 230 V supply ..............................10 Connection overview ..........................10 Connection of smoke vent buttons ......................11 Connection of fire detector / Connenction of fire alarm system ..............12...
  • Page 3: Introduction / Assembly Scheme

    For all D+H SHEV systems, which have been service. The highest national and international installed by a D+H service and sales partner and are quality standards are therefore reliably fulfilled. regularly serviced, you will receive extended warranty services.
  • Page 4: Intended Use / Safety Notes

    D+H maintenance notes. Only original in case of fire. Size, kind and arrangement of the D+H spare parts may be used. Repair is to be opening is of decisive significance for an optimal carried out exclusively by D+H.
  • Page 5: Technical Data

    Continuous duty - Alarm / Ventilation Short-time duty (30 % DC) Temperature range -5 ... +40 °C * D+H Highspeed (HS) drives will be supported. ** The total current of the control panel must not be exceeded. Housing GEH-KST GEH-S-RWA...
  • Page 6: Mounting Of Shev Control Panel With Housing Geh-Kst

    ‫א ת‬ Ν Ο ‫ה ו צ‬ Υ Ø max. 5 mm (not included) Install batteries: Position of the central pcb: ZP RZN 4404-K V2 2x 1,2 Ah / 2x 3,4 Ah 2x 2,2 Ah 6/17 RZN 4404-K 99.823.80 3.7/06/19...
  • Page 7: View Motherboard

    Line Signals Battery Rauchabzugszentrale Smoke Vent Controller F.315A RZN 4404-K/KS V2 IN : OUT : VDS-Nr.: Temp. -5°C...40°C D+H Mechatronic Germany +49 40 605 65 0 2x12V/ www.dh-partner.com x.xAh – LED battery fault Fuse battery Battery charging Battery – : Emergency-supplied potential -...
  • Page 8: Dip Switch Settings

    DIP switch settings Delivery condition S1 1 = ON OPEN-running time limitation in ventilation operation (Only if DIP switch 6 = ON). Using a potentiometer, running time in OPEN direction can be limited. If the vent button is actuated in OPEN direction, the drive will run open as long as the running time is set.
  • Page 9: Cables For D+H Smoke An Heat Vent Systems / Wiring Plan (Paragon)

    Cables for D+H smoke an heat vent systems When selecting and installing the cables, the Group cable (control panel - drive) regional electrical installation regulations At least three wire design: concerning wiring systems and the necessary - 2 wires for the supply of the drive...
  • Page 10: 230 V Supply

    230 V, 50 Hz Only with KS-Version. Seperate electric circuit.. Mark fuse. Connection overview EM 47 K Drive SD-O 371 RT 45 LT 84-U (-SD) Mot.a Mot.b 10kW Mot.a Mot.b – – N– RZN 4404-K V2 10/17 RZN 4404-K 99.823.80 3.7/06/19...
  • Page 11: Connection Of Smoke Vent Buttons

    Max. 8 buttons per line connectable. Standard connection Parallel connection RT 45 RT 45 RT 45 10kW 10kW RZN 4404-K V2 RZN 4404-K V2 * Shunt connection by customer Parallel connection of 2x 2 buttons RT 45 RT 45 last button each 10kW...
  • Page 12: Connection Of Fire Detector / Connenction Of Fire Alarm System

    VdS 2581. For this, the N– N+ Z + M D1 D2 drives must be blockage safe. All D+H drives meet this precondition. Otherwise the DIP switches has to be switched on OFF. Mounting of the drives:...
  • Page 13: Information For Starting

    Information for starting Carry out following sight and performance checks for switching-on the smoke and heat vent control panel. Partial or incomplete connection of components can cause malfunction. All cables connected? Check following connections: mains 230 V, drives, smoke vent buttons, when necessary fire detectors and vent buttons.
  • Page 14 Operation - Release in case of alarm Manual opening by smoke vent button: SMOKE VENT D47 D42 D20 Reset System Line Automatic opening by fire detector: D47 D42 D20 Reset System Line Automatic opening by external control (e.g. fire alarm system): External control D47 D42 D20 Reset...
  • Page 15: Operation

    Operation - Closing after alarm Open the housings (control panel and buttons) using the enclosed keys. With manual release: In case of automatic release by fire detector or external control: Reset = OFF / ON External control Reset System Line ~ 1 Sec.
  • Page 16 Operation - Day-to-day ventilation Ventilation button or SHEV button with ventilation function RT 45-LT required. Open: Close: Stop: ST OP ST OP ST OP SMOKE VENT SMOKE VENT SMOKE VENT Operation - Weather automatic Only if wind detector or rain detector available. Upon triggering of the corresponding sensor, the group of the control panel is closed.
  • Page 17: Inspection / Maintenance

    - Functional testing of connected system D+H authorized expert companies have been components specially trained by D+H for carrying out expertly - Record of competent carrying-out of this maintenance, and they get automatically the maintenance, and designation according to latest maintenance instructions.

This manual is also suitable for: