PID-95P, PID-95
Point Identification Device
General
The Gamewell-FCI PID-95P addressable Point Identification Device is the interface
between the non-powered, normally-open, dry-contact devices. It is designed to
operate with the Gamewell-FCI's 600 Series and ILI95-E3 Series® of analog
addressable fire alarm control panels (FACPs). Point Identification Devices monitor a
single Style B circuit, and they are designed to be mounted in an electrical backbox.
The PID-95P can be surface or flush-mounted and it has a visible LED for alarm/
annunciation.
Operation
The Point Identification Device connects to the Signaling Line Circuit (SLC) via two
wires. The PID-95 will monitor, via a two-wire supervised SLC circuit, contact-type
devices such as a water flow switch or a manual station. Upon activation of the
monitored device, the PID-95 will report its address to the 600 Series or ILI95-E3
Series FACP via the analog SLC. The fire alarm control panel will then activate into all
alarm programmed outputs related to the PID-95.
Programming
To program the PID-95, set a single DIP switch on the device's printed circuit board.
Use the DIP switch to set the address of the device and the priority interrupt (DIP SW
#8). To program the 600 Series or ILI95-Series, use the laptop computer to program
or use the control panel Operator's display.
Standard Application
The PID-95 is the interface between the dry-contact type devices and the SLC of the
fire alarm control panel. Use the PID-95 to connect and to identify monitor points
without the use of conventional input modules at the main control panel. The use of
PID-95s can dramatically reduce the field wiring required on many projects.
Ordering Information
PID-95:
Addressable point identification device for monitoring contact devices
PID-95P:
Addressable input interface device mounted on 4.688" (11.908 cm) plastic plate
70839:
Trim ring for flush-mounting on the PID-95P
FEATURES & BENEFITS
• Compatible with the
• Offers a plate-mounted
Gamewell-FCI, 600
version available for
Series and ILI95-E3
surface or flush
Series Systems
mounting in the
following dimensions:
- 4" x 4.688" (10.16 cm
- 4" x (10.16 cm)
Addressable Devices
• Includes an LED for
alarm annunciation
• Field programmable
x 11.908 cm) double-
gang backbox
square backbox
PID-95P
• Provides priority
• Monitors dry-contact
interrupt
devices
PID-95