Interrupts, error messages, diagnostics and system alarms
5.3 Alarms
USI structure = W#16#0006
Table 5- 12
USI structure = W#16#0006
Data block name
USI
The slot of the I/O module follows.
Slot
2 reserved bytes follow.
Reserved
Reserved
USI structure = W#16#0007
Table 5- 13
USI structure = W#16#0007
Data block name
USI
The slot of the I/O module follows
Slot
If slot 0 is specified, check the width of the station configuration (maximum 1 m).
2 reserved bytes follow.
Reserved
Reserved
44
Content
Comment
W#16#0006
Manufacturer-specific diagnostics if an ET 200SP I/O mod-
ule is installed on an incorrect BaseUnit.
Result: Station stop
W#16#0001 to
Bit 8 to 15
W#16#0040
Bit 0 to 7
Content
Comment
W#16#0007
Manufacturer-specific diagnostics if operation is not possi-
ble with existing bus configuration
Result: Station stop
W#16#0001 to
Bit 8 to 15
W#16#0040
Bit 0 to 7
The I/O modules fail → substitute value behavior
The interface module is still exchanging data with the
IO controller
The I/O modules fail → substitute value behavior
The interface module is still exchanging data with the
IO controller
IM 155-6 PN HF interface module (6ES7155-6AU00-0CN0)
Bytes
2
1
1
1
1
Bytes
2
1
1
1
1
Manual, 03/2015, A5E03915895-AF