Maximum Configuration - Siemens SIMATIC ET 200SP Manual

Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Product overview
2.1 Properties
Properties
The module has the following technical properties:
● Connects the ET 200SP distributed I/O system with PROFINET IO.
● Supply voltage 1L+ 24 V DC (SELV/PELV). The connection plug is included in the scope
of delivery of the interface module.
● PROFINET IO connection via selectable BusAdapters
– For RJ45 bus connection plug (BA 2×RJ45)
– For direct connection of the bus cable (BA 2×FC)
– For fiber-optic cables POF/PCF (BA 2xSCRJ)
– For transition from fiber-optic cable POF/PCF to the RJ45 bus connection (BA
– For transition from fiber-optic cable POF/PCF to the direct connection of the bus cable
● As of firmware version V 3.0, you can plug a light-colored or a dark-colored BaseUnit into
slot 1.
For a list of the functions supported, see (Page 13)

Maximum configuration

● 64 ET 200SP I/O modules
● 1 m backplane bus (without interface module)
Note
Incompatible I/O modules
A list of I/O modules that do not allow a configuration with more than 32 I/O modules is
available in section Compatibility of modules (Page 47).
10
SCRJ/RJ45)
(BA SCRJ/FC)
IM 155-6 PN HF interface module (6ES7155-6AU00-0CN0)
Manual, 03/2015, A5E03915895-AF