Technical Data Sheet - BFI Automation CFC 2000 Technical Description

Compact flame controller
Hide thumbs Also See for CFC 2000:
Table of Contents

Advertisement

Spectral Sensitivity
UV
UV1
IR
IR1
Viewing angle
Power supply
Current consumption
Ambient temperature range
Current output
Failure output
Sensitivity switch over
Flame relay
Switching thresholds
Safety switch off time
Sight tube connection
Purge air connection
Value of purge air
Electrical connection
Standard
Flame proof housing
Dimension
Standard with flange
Flame proof housing
Class of protection
Weight
Standard
Flame proof housing
Full electronically self-check function for the guarantee of the faultless function of the device after VDE
0116, EN 230, EN 298, it correspond the guidelines TRD 411 to 414 and filled the additional require-
ments of TRD 604 for the 72- hours operation. DIN DVGW and DIN-CERTCO approved, CE conform.

Technical Data Sheet

270 to 420 nm
190 to 500 nm
300 to 1050 nm
1050 to 2700 nm
24 V DC +/-15%
ca. 300 mA
-20°C...+70°C
0(4)...20 mA (Ra < 250 Ohm)
Current window possible adjustment by software
24 V DC, short circuit protected
Selection of the sensitivity switch over 24 V DC
1 change over contact, floating
VDE 0110, class A
max. 48 V switching voltage
max. 1 A switching current
max. 30 W switching power
programmable by software
factory adjusted to 1s
1" inside screw ISO 228
1/2" inside screw ISO 228
10 Nm 3 /h
dust proof Harting connector
3m special cable
235 x 108 mm (Length x Diameter)
223 x 120 mm (Length x Diameter)
IP 65, NEMA 4
1,0 kg
3,5 kg
BFI
Automation
technology for your future