To configure the data log for a submeter:
1. Select Log Setup from the Meter Setup menu.
2. Configure the list of parameters to be recorded in the data log file. See Parameters for Data Monitoring and Logging in
Appendix C for a list of the available parameters.
3. Add the name for your data log file in the Name box. It will appear in the data log reports.
4. Save your new setup to the device database, and send it to the meter.
5. Configure a setpoint for periodic triggering the Data recorder using the MINUTE INTERVAL trigger (see Using Alarm/Con-
trol Setpoints).
Remote Device Control
This section describes some online operations on the Multi-Mon you can perform through Power Software. To access device
control options you should have your device online.
Viewing and Clearing Device Diagnostics
To view or clear the device diagnostics status, check the On-line button on the Power Software toolbar and select Device Control
from the Monitor menu.
Refer to Device Diagnostic Codes in Appendix F for the list of diagnostic codes and their meanings. See Device Diagnostics in
Section 2 for more information on the Multi-Mon built-in diagnostics.
Click on the Clear button to clear the device diagnostics. You must be connected to the Multi-Mon using the device base address
to be able to clear the diagnostics status.
Fig. 35.
41
MULTI-MON
31-00035—01