MULTI-MON
Transformer Correction
Transformer correction allows you to compensate ratio and phase angle inaccuracies of the user voltage and current instrument
transformers. To enter the menu, select the T.Corr. entry from the main menu, and then press the ENTER button. For instructions
on navigating in the menu, see Viewing and Changing Setup Items.
The following table lists available options.
Label
Ratio V1-V3
V1-V3 voltage transformer
ratio correction factor
Angle V1-V3 V1-V3 transformer phase
angle error, minutes
Ratio I1-I36
I1-I36 current transformer
ratio correction factor
Angle I1-I36
I1-I36 transformer phase
angle error, minutes
31-00035—01
Basic Device Settings
This menu allows you to define the general characteristics of the electrical network.
To enter the menu, select the Basic entry from the main menu, and then press the ENTER button.
For instructions on navigating in the menu, see Viewing and Changing Setup Items.
The following table lists available options.
Label
Parameter
PT
Pt Ratio
Frequency
Nominal frequency
PowDmdPer Block power demand
period
Num.Per.
The number of blocks
in the sliding window
VDmnPer.
Volt demand period
ADmdPer.
Ampere demand
period
Parameter
Options
0.700 to 1.300
-600 to 600
0.700 to 1.300
-600 to 600
Options
Default
1.0-6500.0
1.0
50, 60 Hz
60 Hz
1, 2, 5, 10,
15, 20, 30,
30
60 min
1-15
1
0-9000 sec
900
0-9000 sec
900
Default
The ratio of the true transformer ratio to the marked
1.000
ratio.
The phase displacement, in minutes, between the
primary and secondary values. The phase angle of
0
a voltage transformer is positive when the
secondary value leads the primary value.
The ratio of the true transformer ratio to the marked
1.000
ratio.
The phase displacement, in minutes, between the
primary and secondary values. The phase angle of
0
a current transformer is positive when the
secondary value leads the primary value.
20
Description
The phase potential transformer's
primary to secondary ratio
The nominal power frequency
The length of the demand period
for power demand calculations
The number of blocks to be
averaged for sliding window
demands
The length of the demand period
for volt demand calculations
The length of the demand period
for ampere demand calculations
Description