Connect the control cables
H
on page 438. It shows an example with one analog signal cable and one
See figure
digital signal cable. Make the connections according to the macro in use. The default
connections of the ABB standard macro are shown in section
on page 182.
1. Remove the front cover, if not already removed. See section
and open the cover
Example of connecting an analog signal cable:
2. Cut an adequate hole into the rubber grommet and slide the grommet onto the
cable. Slide the cable through a hole in the cable entry and attach the grommet to
the hole.
3. Ground the outer shield of the cable 360 degrees under the grounding clamp.
Keep the cable unstripped as close to the terminals of the control board as
possible. Ground also the pair-cable shields and grounding wire at the SCR1
terminal.
4. Route the cable as shown in the figure.
5. Connect the conductors to the appropriate terminals of the control board and
tighten to 0.5...0.6 N·m (0.4 lbf·ft).
6. Tie all control cables to the provided cable tie mounts.
on page 177.