Operating menu
Process property
Navigation
Description
Selection
Additional information
DC value lower medium
Navigation
Prerequisite
Description
User entry
Additional information
154
"Interface" submenu
Navigation
Setup → Advanced setup → Interface
Setup → Advanced setup → Interface → Process property
Specify typical rate of change for the interface position.
• Fast > 1 m (40 in)/min
• Standard < 1 m (40in) /min
• Medium < 10 cm (4in) /min
• Slow < 1 cm (0.4in) /min
• No filter / test
The device adjusts the signal evaluation filters and the damping of the output signal to the
typical rate of level change defined in this parameter:
Process property
Fast > 1 m (40 in)/min
Standard < 1 m (40in) /min
Medium < 10 cm (4in) /min
Slow < 1 cm (0.4in) /min
No filter / test
Setup → Advanced setup → Interface → DC lower medium
Operating mode (→ 131) = Interface or Interface with capacitance
Specify the dielectric constant ε
1 to 100
For the dielectric constants (DC values) of many media commonly used in industry,
please refer to:
• Dielectric constant (DC value) Compendium CP01076F
• The Endress+Hauser "DC Values app" (available for Android and iOS)
The factory setting, ε
Levelflex FMP51, FMP52, FMP54 PROFIBUS PA
Step response time / s
5
15
40
74
2.2
of the lower medium.
r
= 80, applies for water at 20 °C (68 °F).
r
Endress+Hauser