Levelflex FMP51, FMP52, FMP54 PROFIBUS PA
Endress+Hauser
Problem
The total level jumps to the
interface level in the case of
thin interfaces.
Interface measured value
jumps.
Possible cause
The thickness of the upper medium
is lower than 60 mm.
Emulsion layer present.
Diagnostics and troubleshooting
Remedy
Measurement of the interface is only
possible for interface heights greater
than 60 mm.
Emulsion layers impair the
measurement.
Contact Endress+Hauser.