Mitsubishi Electric MELSEC iQ-F Series Handbook page 95

Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

FX3 Series
IVCK
IVDR
IVRD
IVWR
IVBWR
IVMC
ADPRW
PR
COMRD
COMRDP
REFF
REFFP
DHSCT
PLSR
DPLSR
RS
VRRD
VRRDP
VRSC
VRSCP
ZRN
DZRN
HKY
DHKY
TKY
DTKY
ARWS
RD3A
RD3AP
WR3A
MELSEC iQ-F
IVCK
IVDR
IVRD
IVWR
IVBWR
IVMC
ADPRW
OUT SM4095
OUT SM4095
OUT SM4095
OUT SM4095
OUT SM4095
OUT SM4095
OUT SM4095
OUT SM4095
OUT SM4095
OUT SM4095
OUT SM4095
OUT SM4095
OUT SM4095
OUT SM4095
OUT SM4095
OUT SM4095
OUT SM4095
OUT SM4095
OUT SM4095
OUT SM4095
OUT SM4095
OUT SM4095
OUT SM4095
Appendix 1 Instruction Replacement List
Remarks
SM4095 is added to parameters of
instructions. Change to an
appropriate device or label.
These instructions are not supported
by MELSEC iQ-F. Therefore, it will be
replaced to OUT SM4095.
Correct the program to use REF
instruction.
Correct the program to use REFP
instruction.
Set the high-speed comparison table
or multi-point output high-speed
comparison table in the module
parameter "High-speed I/O".
Correct the program to use DRVI
instruction. Set the acceleration/
deceleration time specified by the
PLSR instruction operand as the
acceleration time and deceleration
time of SD.
Correct the program to use DDRVI
instruction. Set the acceleration/
deceleration time specified by the
DPLSR instruction operand as the
acceleration time and deceleration
time of SD.
Correct the program to use RS2
instruction.
These instructions are not supported
by MELSEC iQ-F. Therefore, it will be
replaced to OUT SM4095.
Correct the program to use DSZR
instruction. Use the same device for
near-point dog signal and zero point
signal of the DSZR instruction, and
set the zero point signal count start
time to the rear end and the zero
point signal count to 1.
Correct the program to use DDSZR
instruction. Use the same device for
near-point dog signal and zero point
signal of the DDSZR instruction, and
set the zero point signal count start
time to the rear end and the zero
point signal count to 1.
Create the program using the input
device (X).
Correct the program to use FROM
instruction.
Correct the program to use FROMP
instruction.
Correct the program to use TO
instruction.
APPX