Section 2. Unit Location Considerations

2.1 Unit Dimensions and Weight
Table 2.1
Unit Dimensions and Weight
Models
H x D x W (in)
5TTR3018A
29 x 26 x 29
5TTR3024A
29 x 26 x 29
5TTR3030A
29 x 30 x 33
5TTR3036A
29 x 30 x 33
5TTR3042A
37 x 30 x 33
5TTR3048A
37 x 34 x 37
5TTR3060A
37 x 34 x 37
* Weight values are estimated.
When mounting the outdoor unit on a roof, be
sure the roof will support the unit's weight.
Properly selected isolation is recommended to
alleviate sound or vibration transmission to the
building structure.
2.2 Refrigerant Piping Limits
1. The maximum TOTAL length of refrigerant
lines from outdoor to indoor unit should
NOT exceed 150 feet (including lift).
2. The maximum vertical change should not
exceed 50 feet.
3. Service valve connection diameters are
shown in Table 5.1.
Note: For other line lengths, Refer to Refriger-
ant Piping Application Guide, SS-APG006-EN
or Refrigerant Piping Software Program,
32-3312-03 (or latest revision).
18-AC127D1-1A-EN
Weight* (lb)
133
133
161
161
184
211
211
W
H
D
Standard
Line Set
150' Max
TOTAL Line Length