Startup/Operation/Backwash; Electrical - STA-RITE JSAL15D-06 Owner's Manual

Waterford systems high rate sand filter system
Table of Contents

Advertisement

8. System is ready for startup.
N O TICE: If there are leaks from beneath valve/clamp
area, STOP PUMP , release all pressure, remove clamp
and valve and clean sealing surfaces.
Follow directions under " Valve Installation" , Page 6,
when reinstalling valve. See Figures 6 and 7.
1. Install O-Ring
on valve flange.
2. Install valve on tank.
Tank flange must
be clean; insert
collector pipe
into bottom
of valve.
Figure 6
Port labeled
A q u a t o o l s
"PUMP" should
.WATERFORD, WI.
53185
USA
point toward
pump.
1/4" Max.
Install clamp
If unable to
and tighten
close gap
until clamp
to 1/4" or less,
ends (under
wait 15-30
bolt) are 1/4"
minutes and
apart.
retighten.
Figure 7
A q u a t o o l s
.WATERFORD, WI.
53185
USA
735 0294
Tap around
clamp while
tightening to
help seat
clamp.
736 0294

ELECTRICAL

Hazardous voltage.
Can shock, burn,
or cause death.
Disconnect power
before working
on pump or motor.
W iring:
Install a Ground Fault Circuit Interrupter (GFCI) in cir-
cuit; it will sense a short-circuit to ground and discon-
nect power before it becomes dangerous to pool users.
For size of GFCI required and test procedures for GFCI,
see manufacturer's instruction.
In case of power outage, check GFCI for tripping (which
will prevent normal water circulation). Reset if neces-
sary.
Match circuit breaker size to Table III below.
• Do not modify cord, plug, or receptacle. If an existing
circuit must be used and the receptacle and plug do
not match exactly, consult a licensed electrician.
• Do not use an extension or drop cord with this system;
it could cause a fire hazard or low voltage problems.
Wet cords cause shock hazards. Extension cords can
easily become cut or frayed and dangerous when
placed across yard areas or walkways.
Voltage:
Voltage at motor must be not more than 10% above or
below motor nameplate rated voltage or motor may
overheat, causing overload tripping and reduced compo-
nent life. If voltage is less than 90% or more than 110%
of rated voltage when motor is running at full load, con-
sult power company.
Table III–Recommended Fusing D ata, 115 Volt 60 H z M otors.
Pump
M odel N o.
17290-J 075
17290-J 100
17290-J 150
17290-J 1002 (2-Speed)
N O TICE: Values given are for pump motor only. Do not put
any other accessories on this circuit.
7
Risk of electrical shock.
Plug pump into a
grounded, GFCI-protected 115
Volt circuit only. Incorrect
voltage can cause fire or seri-
ously damage motor and voids
warranty. Protect cord from
water and physical damage.
GFCI tripping indicates
an electrical problem. If
GFCI trips and will not reset,
have a qualified electrician in-
spect and repair electrical sys-
tem.
Risk of electrical
shock. U nplug motor before
servicing or repairing pump or
motor.
Branch
M otor
Full Load
Circuit Breaker
H .P.
Amps
Rating (Amps)
3/4
9.4
1
13.2
1-1/2
13.5
1 – 1/6
11.6/3.3
15
20
20
15