Specifications Of The Triton - Rheem TRITON GHE80SS Service Training Manual

80, 100 & 119 gallon ultra-high efficiency water heaters
Hide thumbs Also See for TRITON GHE80SS:
Table of Contents

Advertisement

SPECIFICATIONS OF THE TRITON

Models
Fuel Type
Gallon Capacity
Rated Gas Input (Btu/Hr.)
Ignition System
Heat Exchanger
Diagnostics
Installation
Gas Connection
Inlet Gas Pressure
High Altitude
Water Connection
Vent Material Allowed
Maximum Vent Lengths
Noise Level
Water Temperature
Electrical
Safety Devices
GHE (gas high efficiency gas) 80, 100 and 119 gallon (tank capacity)
Powered direct vent; sealed combustion; fully condensing; ASME rating options on all inputs;
Natural and L.P. gas; thermal efficiency based on model
130,000; 160,000; 199,900; 250,000; 300,000; 350,000; 399,900; 499,900
Spark ignition to main burner; no pilot of any kind
Nonvolatile storage of heater settings and fault history. Diagnostic codes provided through an
onboard LCD display consisting of information on power to the control, control status, fault codes
2" NPT inlet/outlet – side connect – front and rear
Polypropylene, PVC, ABS, CPVC plastic pipe options
60 db @ 15 feet (max) using test ANSI S12.34/ISO 3744
Factory Setting
Digital Thermostat (adjustable)
Temperature Differential
Electrical Rating
Wire
Earth Ground Sensitive
Polarity Sensitive
Temperature and Pressure Relief Valve – 150 PSI or 210°F
Venting Over Temperature Switch; trips at 160°F; automatic reset
Energy Cut Off for high water temperature; trips at 205°F (auto reset) +- 3°F
Flame Rectification - The presence of a flame is measured via a flame rod that points into the
flame. Control measures => 0.5 micro amp (uA)
5
power vent options on all inputs.
80,100 and 119 gallons
Down fired, multi-pass heat exchanger
and system settings.
Indoor only
3/4" NPT Female and 1 1/4" NPT Female
Natural Gas Min. 3.5" w.c. Max. 10.5" w.c.
L.P. Gas Min. 11.0" w.c. Max. 13.0" w.c.
Units rated to 8,999ft. GHE119 up to 10k ft
1.5" for Top (Plugged from factory)
130-160kbtu – 2", 3" & 4" venting options
199-499kbtu – 3", 4" & 6" venting options
SEE USE AND CARE MANUAL
SEE USE AND CARE MANUAL
Fuse protected main controller
120°F
1 degree increments
85°F to 185°F
Factory Setting of 12°F
User selectable from 1°F to 30°F
120 VAC 50/60Hz, 7 Amps
3 (three) wire (hot, neutral, ground)
Yes
Yes
Rheem TRITON
TM
Service Manual