BACNET CONFIGURATIONS
BACNET SETTINGS DETAILS:
BACnet Setting
BACnet MAC Address
BACnet Baud Rate
BACnet Config
BACnet Max Master
Address
BACnet Device Instance
Default Value
Range: 0 to 127 for MS/TP Master and 0 to 254 for MS/TP Slave
When possible, 0 should be avoided.
1
Must be unique among all devices on a given BACnet network segment.
kbps: kilo-bits per second
38.4 kbps
Options: 9.6 kbps, 19.2 kbps, 38.4 kbps, 57.6 kbps, 76.8 kbps, or 115.2
kbps
MS/TP Master
Options: MS/TP Master or MS/TP Slave
Only applicable if BACnet Config is set to MS/TP Master.
127
Range: 0 through 127
Range: 0 through 4,194,303
The default value indicates unassigned instance, and should not be used.
4,194,303
Instance must be assigned for use.
Must be unique across devices on all BACnet network segments of the
BACnet internetwork.