Connection Instructions-Refrigerant Piping - Mars Comfort-Aire Century VCD24 SA Series Installation Manual

Hyper heat single zone air handler & condenser
Hide thumbs Also See for Comfort-Aire Century VCD24 SA Series:
Table of Contents

Advertisement

Installation and Operation Manual - VCDxxSA
Connection Instructions—Refrigerant Piping
Step 1: Cut pipes
When preparing refrigerant pipes, take
extra care to cut and flare them properly.
This will ensure efficient operation and
minimize the need for future maintenance.
Measure the distance between the
indoor and outdoor units.
Using a pipe cutter, cut the pipe a
little longer than the measured
distance.
Make sure that the pipe is cut at a
perfect 90° angle.
90°
Oblique
DO NOT DEFORM PIPE
WHILE CUTTING
Be extra careful not to damage, kink, or
deform the pipe while cutting. This will
drastically reduce the heating
performance
Rough
Warped
Step 2: Remove burrs
Burrs can affect the air-tight seal of refrigerant piping
connection. They must be completely removed.
Hold the pipe at a downward angle to prevent
burrs from falling into the pipe.
Using a reamer or deburring tool, remove all burrs
from the cut section of the pipe.
Point down
Step 3: Flare pipe ends
Proper flaring is essential to achieve an airtight seal.
After removing burrs from cut pipe, seal the ends
with PVC tape to prevent foreign materials from
entering the pipe.
Sheath the pipe with insulating material.
Place flare nuts on both ends of pipe. Make sure
they are facing in the right direction, because you
can't put them on or change their direction after
flaring.
Flare nut
Copper pipe
Remove PVC tape from ends of pipe when ready
to perform flaring work.
18
Pipe
Reamer

Advertisement

Table of Contents
loading

Table of Contents