38MGRBQ: Service Manual
Indoor / Outdoor Units Communication Protection
If the indoor units do not receive the feedback signal from the outdoor
units for two consecutive minutes, the unit stops and displays a failure
code.
High Condenser Coil Temperature Protection
T3
Fig. 25 — High Condenser Coil Temperature Protection
Outdoor Unit Anti-Freezing Protection
When T2<39°F (4°C) for 250 seconds or T2< 32°F (0°C), the indoor unit
capacity demand is zero and resumes the normal operation when
T2>46.4°F (8°C) and the protection time is no less than three minutes.
Oil Return
Rules for Operation:
1. If the compressor frequency remains lower than the frequency set for
the setting time, the unit raises the frequency to the frequency set for
the setting time and then resumes the former frequency.
2. The EXV continues at 300p while the indoor units maintain their
operation. If the outdoor ambient temperature is higher than the set
frequency during the oil return, the unit stops the oil return process.
Low Outdoor Ambient Temperature Protection
When the compressor is off and T4 is lower than -31°F (-35°C) for ten
seconds, the unit stops and displays "LP."
When the compressor is on and T4 remains lower than -40°F (-40°C)
for ten seconds, the unit stops and displays "LP."
When T4 is no lower than -25.6°F(-32°C) for ten seconds, the unit
exits protection.
Controls and Functions
Capacity Request Calculation
Cooling Mode
T1 Ts
3
2
1
0
1
Fig. 26 — Cooling Mode
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Off
Decrease
Hold
Resume
a
4
3
b
2
c
1
d
e
0
f
Table 17 — Cooling Mode
CAPACITY AREA
NORM CODE (N)
Table 18 — Cooling Mode
MODEL
9K
HP
1.0
NOTE: The final result is an integer.
Use Table 19 and the final capacity request to confirm the operating
frequency.
Table 19 — Cooling Mode
Frequency
0
COOL_F1
(Hz)
Amendatory
Capacity
0
1
Demand
The maximum running frequency is adjusted according to the outdoor
ambient temperature.
Fig. 27 — Maximum Running Frequency
21
a
b
c
d
e
3
2
1.5
1
0.5 0
12K
18K
1.2
1.5
...
COOL_F2
COOL_F24
COOL_F25
...
...
2
24
...
T4FREMAXC0
f
24K
2.5
25

Advertisement

Table of Contents
loading

This manual is also suitable for:

38mgrbq24c-338mgrbq30d-338mgrbq36d-338mgrbq48e-3

Table of Contents