DC/AC Inverter
PWS series
User Manual
Page 15 (24)
3.3 LED indications
The following functions are indicated with front side LED indicators:
LED
Colour
Designation
green
OPERATION
green
Vout
red
Vin>
red
Vin<
red
Error
OVERLOAD/
red
TEMP.
red
COLL. FAILURE
*
Maximum contact load: Vmax. 110V
ELTEK VALERE INDUSTRIAL ©2008
Meaning
Inverter is switched ON, internal supply voltage available
Inverter output voltage available
Input overvoltage; inverter switched OFF
Input undervoltage; inverter switched OFF
Output voltage distorted due to short circuit or overload at the output
Overheating of the inverter /continuous overload.
Collective failure: The delay time is 20s; the relay contact
same time. The following failures are combined: Vin<, Vin>, ERROR,
OVERLOAD/TEMP.
/Imax. <0.45A
DC
Vmax. 60V
/Imax. <1A
DC
Vmax. 24V
/Imax. <8A
DC
DC
DC
DC
*
reacts at the
UM_PWS_E_R1.2