Serial interface for operation of the detection system ■ Optional Ethernet interface ■ Little wiring required ■ Central data compiling and visualization with PC software ■ Repeater feature to expand range ■ Port for 24V-UPS ■ 420-2410-003 EN21 ADICOS M-BUSMASTER XF...
Objective This manual describes how to properly install, wire, start up and operate the ADICOS M-BUSMASTER XF. Once the device has been successfully started up, this document serves as a reference in the event of malfunctions. It is intended to be used only by properly qualified personnel. (–› Chap. 2, For your safety) Explanation of Symbols This manual follows a certain structure to make it easy to work with and understand.
ADICOS M-BUSMASTER ADICOS NT V40-A3 - power supply for special fire detector Storing this Manual Store this manual near the fire detectors, in a place where it can easily be accessed when needed for reference. 420-2410-003 EN21 ADICOS M-BUSMASTER XF...
Intended use also includes following the instructions in this manual and complying with all relevant local regulations. The ADICOS M-BUSMASTER XF may not be used for any other purpose. If the device is used in any other way, or if changes are made to the product, including in the course of installation and maintenance, the warranty claim is no longer valid.
■ Only use original spare parts and original accessories! ■ Original spare parts and accessories may only be in- stalled by trained specialist personnel. ■ Qualified personnel are persons as described in Chap. 2.3. 420-2410-003 EN21 ADICOS M-BUSMASTER XF...
DC 24 V. When systems are spread out over a large area, the M-BUSMASTER XF can also be used as a repeater. Because it is so durable, the device is protected from dust and moisture penetration, and it can easily withstand harsh environments. 420-2410-003 EN21 ADICOS M-BUSMASTER XF...
Cable duct Slot for Ethernet card (optional) Scope of Delivery Check that the delivery is complete and no items are damaged. The scope of delivery includes: M-BUSMASTER – Optional: LAN card – Instruction manual – 420-2410-003 EN21 ADICOS M-BUSMASTER XF...
Power feed: DC 24 … 27 V; check proper polarity (Refer to circuit board label) Current consumption: max. 4 A X2 – M-Bus output on ADICOS M-BUSMASTER XF Connection for two-wire bus system, for communication with the detectors. Bus voltage: DC 40 V;...
Page 13
RS-232 PC connection X4:6 RS-232 PC connection Not assigned X4:7 RS-232 PC connection X4:8 RS-232 PC connection Not assigned X4:9 RS-232 PC connection Not assigned X5:1 M-Bus input “Slave” M-Bus A X5:2 M-Bus input “Slave” M-Bus B 420-2410-003 EN21 ADICOS M-BUSMASTER XF...
RS-232 interface. Fuse Yellow Output fuse has triggered. Overload Overload: The current consumption is greater than 1.5 A. To remedy this issue, remove consumers from the bus. Normal Green Device is ready. 420-2410-003 EN21 ADICOS M-BUSMASTER XF...
DeSCRipTion of pRoDuCT Jumper 3.5.1 Jumper Settings “Interface” The interface through which the ADICOS M-BUSMASTER XF communicates can be configured with the jumpers A0 and A1. Fig. 4 The setting “Operation via RS-232 interface” corresponds to classic master operation. The data from the detector connected to the M-Bus is transferred for further processing via the RS-232 interface to a PC with ADICOS System Software.
• De-energize the detector löschen: entire detector system for any installa- tion work! Requirements of Mounting Location The ADICOS M-BUSMASTER XF is not approved for use in potentially explosive areas and may never be used in such areas. 5.1.2 Protective Measures To ensure smooth operation of the ADICOS M-BUSMASTER XF, always consider the following factors when choosing a place to attach the device.
DeSCRipTion of pRoDuCT Vibration The electronics contained in the ADICOS M-BUSMASTER XF can be damaged when subjected to vibration. If there are any sources of strong vibration near where the device is installed, it has to be positioned such that it is immune to the vibration.
5.3.3 Optional LAN Connection with Ethernet Card The ADICOS M-BUSMASTER XF can be ordered with an Ethernet card if needed. The addition- al board is in the slot and the internal connecting cables are attached before the device leaves the factory. The LAN cable still has to be connected.
The serial RS-232 interface is standard on the ADICOS M-BUSMASTER XF. Connect the ADICOS M-BUSMASTER XF to the COM port on the service PC and start the System Software. First set the interface parameters in the software as needed. Select the COM port used and a baud rate of 4800 baud.
Page 21
6.3.2 Integrating M-BUSMASTER XF via Optional LAN The ADICOS M-BUSMASTER XF can be equipped with an Ethernet connection upon request. The network card is based on a module XPort supplied by Lantronix. The MAC address of the network card can be found on the label on the XPort xxx-xx-xxxxx-x-x Fig.
Page 22
Changing IP Address Select the device to be changed from the list. Then click “Assign IP.” The wizard used to adapt the IP address opens. Fig. 11 Select “Assign a specific IP address“ and click “Next.” 420-2410-003 EN21 ADICOS M-BUSMASTER XF...
Page 23
CoMMiSSioning Fig. 12 Enter the desired IP address and the subnet mask, then click “Next.” Fig. 13 Click “Assign.” The new IP address is programmed. Fig. 14 Click “Finish” and close the Device Installer. 420-2410-003 EN21 ADICOS M-BUSMASTER XF...
Page 24
Add ADICOS detectors to the query, e.g. using the autoscan feature. While the service PC is communicating with the connected detectors, the red LED (reply) as well as the yellow LED (query) should be flashing. 420-2410-003 EN21 ADICOS M-BUSMASTER XF...
• Deenergize the entire detector system before cleaning the device! The ADICOS M-BUSMASTER XF enclosure can be cleaned with a soft, damp cloth and dish- washing liquid. Scouring agents, acids and bases may not be used; do not apply water pres- sure to clean.
M-Bus voltage 10 Disposal Return the device to the manufacturer when it reaches the end of its serviceable life. The manufacturer will ensure that the components are disposed of properly, in an environ- mentally friendly manner. 420-2410-003 EN21 ADICOS M-BUSMASTER XF...
-10 … +60 °C Relative humidity: ≤ 95 % relative humidity (non-condensing) Enclosure: Coated die-cast aluminum (corrosion-resis- tant) Dimensions (H x W x D): 72,5 x 208 x 303 mm Weight: 3.3 kg Degree of protection: IP 65 420-2410-003 EN21 ADICOS M-BUSMASTER XF...
Model: Device model SERIAL: Serial number Year of production (variable) (variable) ART-Nr: Article number TEMP: Ambient Degree of (variable) temperature protection VAR: Interface /VA: Voltage range / Input fuse maximum pow- er consumption CE marking: 420-2410-003 EN21 ADICOS M-BUSMASTER XF...