Page 3
The ADICOS HOTSPOT-X0 Interface-X1 is an interface between the ADICOS HOTSPOT-X0 Sensor Unit and the fire control panel within potentially explosive atmospheres of zones 0, 1, and 2.
Objective These instructions describe the requirements on installation, wiring, commissioning, and oper- ation of the ADICOS HOTSPOT-X0 Interface-X1. After commissioning it is used as reference work in the case of faults. It is exclusively addressed to knowledgeable specialist personnel (–› Chap. 2, Safety instructions).
ABOUT THIS MANUAl WARNING! This information type signals a danger that can lead to fatal or severe injuries. DANGER! This information type signals a danger that directly leads to fatal or severe injuries. DANGER! This information type signals measures that must be implemented for maintaining the explosion protection.
− Intended use The ADICOS HOTSPOT-X0 Interface-X1 is intended for use with the ADICOS HOTSPOT-X0 Sensor Unit and is designated for the detection of fire scenarios in potentially explosive atmo- spheres of zones 0, 1, and 2. It may be exclusively operated within ADICOS systems. In this context, the operating parameters described in Chap.
Installation, commissioning, parameterization, and maintenance may only be performed by authorized and respectively trained personnel. Handling electrical voltage DANGER! The electronics of the ADICOS HOTSPOT-X0 Interface-X1 works with a voltage that can trigger an explosion in potentially explosive atmospheres. De-energize the entire detector system and secure −...
ACCESSORIES Accessories WARNING! Only original accessories of the manufacturer may be used! The following accessories are available for the ADICOS HOTSPOT-X0 Interface-X1: Art no. Description 410-2401-310 HOTSPOT-X0 Sensor Unit 83-09-06052 Cable gland for non-reinforced and non-sealed cables 83-09-06053 Cable gland for reinforced and non-sealed cables...
STRUCTURE Structure Overview Description Flameproof enclosure ① Top-hat rail with Ex barriers, connection terminals and interface circuit board ② Thread for enclosure lid ③ Enclosure lid ④ Mounting place for additional cable glands ⑤ Cable gland (2x) ⑥ Mounting bracket (4x) ⑦...
STRUCTURE Connection terminals The connection terminals are located inside the enclosure on the top-hat rail. Beschreibung Ex barrier 1: sensor communication (intrinsically safe circuit 1) ① Ex barrier 2: sensor power supply (intrinsically safe circuit 2) ② System connection ③ 4.2.1 Sensor communication (intrinsically safe circuit 1) Occupation...
Page 12
STRUCTURE 4.2.3 System connection terminal Occupation M-Bus A M-Bus A Alarm A Fault A lOOP A in lOOP A out Shield Shield +24 V +24 V M-Bus B M-Bus B Alarm B Fault B lOOP B in lOOP B out Shield Shield 410-2410-011 EN12...
INSTAllATION Installation WARNING! Installation work may only be performed, if the potentially explosive area is released for work via a risk assessment. De-energize the entire detector system and secure against − unintentional reactivation for all wiring work! Selecting the mounting location WARNING! In contrast to the ADICOS HOTSPOT-X0 Sensor Unit, the ADICOS HOTSPOT-X0 Interface-X1 is not approved for installation within Ex zone 0.
Wiring of ADICOS HOTSPOT-X0 Sensor Unit WARNING! The connection cable must be routed according to DIN EN 60079-14! Only use approved, intrinsically safe connection cables provided − by GTE! Observe minimum bending radius! − Remove enclosure lid by rotating counter clockwise Open cable gland...
„d“ Firmly close enclosure lid before commissioning! − NOTE! The ADICOS HOTSPOT-X0 Interface-X1 is a passive component. A separate commissioning is not required. Initialize the ADICOS fire detection system according to the − operating manual of the installed central unit (ADICOS BMZ-30 /...
MAINTENANCE Maintenance The ADICOS HOTSPOT-X0 Interface-X1 does not require maintenance. Disposal Return device to the manufacturer after the end of the useful life. The manufacturer ensures environmental-friendly dispos- al of all components. 410-2410-011 EN12 HOTSPOT-X0 Interface-X1...
SPECIFICATIONS 10 Specifications General information Enclosure dimensions: 220 x 220 x 180 (L x W x H) Overall dimensions: 270 x 264 x 180 (L x W x H) Enclosure material: Aluminium Weight: Cable bending radius: > 38 Protection class: Information regarding explosion protection Explosion protection class: II 2(1)G Ex db [ia Ga] IIC T4 Gb...