GTE ADICOS HOTSPOT-1000 Installation Operation & Maintenance

Thermographic surface temperature detector
Hide thumbs Also See for ADICOS HOTSPOT-1000:

Advertisement

Quick Links

HOTSPOT-1000
410-2410-001 EN11
Installation - Operation - Maintenance
EN
Thermographic Surface Temperature Detector
HOTSPOT-1000
GTE Industrieelektronik GmbH
Helmholtzstr. 21, 38-40 | D-41747 Viersen, GERMANY | info@gte.de |  +49(0)2162 / 3703-0 | www.gte.de

Advertisement

Table of Contents
loading

Summary of Contents for GTE ADICOS HOTSPOT-1000

  • Page 1 HOTSPOT-1000 410-2410-001 EN11 Installation - Operation - Maintenance Thermographic Surface Temperature Detector HOTSPOT-1000 GTE Industrieelektronik GmbH Helmholtzstr. 21, 38-40 | D-41747 Viersen, GERMANY | info@gte.de |  +49(0)2162 / 3703-0 | www.gte.de...
  • Page 2 Support hotline: +49 (0)2162 /37030 E-mail: service@adicos.de © 2018 GTE Industrieelektronik GmbH – This document and all illustrations contained herein are protect- ed by copyright and may not be copied and pasted, modified or distributed without the express consent of...
  • Page 3 In the central unit the parameterization of each detector is specified. All of the sensor data needed for statistical analyses are also stored in the central unit. The ADICOS HOTSPOT-1000 is an IR fire detector used for optical and spatially resolved fire and heat detection. It is well suited for these applications: ■...
  • Page 4: Table Of Contents

    Commissioning ..........22 410-2410-001 EN11 ADICOS HOTSPOT-1000...
  • Page 5 10.1 Measuring Range ........29 10.2 Precision of Standard Version ADICOS HOTSPOT-1000 ... . 29 10.3 Purge Air Requirements.
  • Page 6: About This Manual

    When it is possible to describe intermediate states or events resulting from the instruction steps (e.g. screens, internal function steps, etc.), they are shown like this: Intermediate state Warnings The following types of notes are used through this manual: NOTE! Indicates information relevant to further operation of the equipment. 410-2410-001 EN11 ADICOS HOTSPOT-1000...
  • Page 7: Abbreviations

    Field Device Network (fire detection bus, SIEMENS fire detection systems) Local Security Network (fire detection bus, BOSCH fire detection systems) Fire detection system Storing this Manual Store this manual near the detectors, in a place where it can easily be accessed when needed for reference. ADICOS HOTSPOT-1000 410-2410-001 EN11...
  • Page 8: For Your Safety

    Intended use also includes following the instructions in this manual and complying with all relevant local regulations. The ADICOS HOTSPOT-1000 may not be used for any other purpose. If the device is used in any other way, or if changes are made to the product, including in the course of installation and maintenance, the warranty claim is no longer valid.
  • Page 9: Qualification Required Of Personnel

    − When in doubt, consult the manufacturer! Accessories and Spare Parts WARNING! Only original spare parts and accessories provided by the manufacturer may be used! WARNING! Original spare parts and accessories may be installed only by properly trained personnel. ADICOS HOTSPOT-1000 410-2410-001 EN11...
  • Page 10: Product Description

    The ADICOS HOTSPOT-1000 is an infrared fire detector with an integrated signal evaluator for which the parameters can be individually configured. Because of its durable design, the ADICOS HOTSPOT-1000 can be used in adverse industrial environments. It is ideal for monitoring bulk goods prone to spontaneous combustion as well as conveyor lines.
  • Page 11: Potential Uses

    But when the air flow is greater or the air rate is faster, the air settling tube can no longer prevent the ADICOS HOTSPOT-1000 optics from getting dirty. The ADICOS HOTSPOT-1000 has a purge air connection to ensure that the optics stay clean even when exposed to strong turbulence and high wind speeds.
  • Page 12 The purge air supply must remain uninterrupted as long as dust residue can be expected. The air flow rate can be restricted with throttle valves; one per detector, e.g. from the Festo series GR-QS4-LF, Festo art. no. 193966. 410-2410-001 EN11 ADICOS HOTSPOT-1000...
  • Page 13: Signal Relays

    M-Bus to the ADICOS service software to be displayed. If the ADICOS HOTSPOT-1000 is connected to a fire panel (ADICOS BMZ-30 or a fire panel from a different supplier), the fire panel controls the detector’s alarm display.
  • Page 14: Configuration And Evaluation

    FUNCTIONING Configuration and Evaluation One of the outstanding features of the ADICOS HOTSPOT-1000 is its capacity to flexibly and quickly detect hot spots. The detector has a separate alarm threshold for each individual pixel. In addition to overtemperature, it also detects flames. Each detector has two sets of limits.
  • Page 15: Installation

    Moisture When choosing a place to attach the ADICOS HOTSPOT-1000, take into consideration that it may not be exposed to moisture. Keep in mind that water could be used for cleaning purposes near the mounting location.
  • Page 16 The electronics contained in the ADICOS HOTSPOT-1000 can be damaged when subjected to vibration. If there are any sources of strong vibration near where the ADICOS HOTSPOT-1000 is mounted, the detector has to be positioned such that it is immune to the vibration.
  • Page 17 So the object resolution of the IR detectors is a factor of the distance. Disruptions Certain disruptive variables can have a negative impact on functioning of the ADICOS HOT-SPOT-1000, leading to a false alarm. When setting the alarm thresholds, take into con- sideration intended heat sources, e.g. motor vehicles. ADICOS HOTSPOT-1000 410-2410-001 EN11...
  • Page 18: Mounting

    Select a suitable mounting location. Install the GTE connection box near the ADICOS HOTSPOT-1000. If applicable, use a 4 mm hose to connect the ADICOS HOTSPOT-1000 to a purge air supply. This prevents residue from forming on the ADICOS HOTSPOT-1000 optics.
  • Page 19: Wiring

    Attaching to a mounting bracket The ADICOS HOTSPOT-1000 is also available with a ball joint. The ball joint is connected to the detector with a screw fitting in the center of the back of the enclosure. There is a lever that can be released to adjust the detector to the proper angle, allowing it the best view of the detection area.
  • Page 20 Blue Fire panel interface A – in Violet Fire panel interface B – out Gray Fire panel interface A – out Blue/red M-Bus Gray/ Max, 40 V, non-polarized pink With series resistor, standard 680 Ω 410-2410-001 EN11 ADICOS HOTSPOT-1000...
  • Page 21 NO (make contact) The pre-alarm relay is linked to set 2 of the trigger limits. The pre-alarm functionality is ensured as long as the limits programmed in set 2 are less sensitive than the limits in set 1. ADICOS HOTSPOT-1000 410-2410-001 EN11...
  • Page 22 INSTALLATION 5.3.2 Attaching ADICOS Connection Cable to ADICOS HOTSPOT-1000 Press the bayonet lock on the ADICOS connection cable against the detector connection. Carefully turn the entire bayonet lock to find the proper position for the twist protection. Firmly turn the bayonet ring on the connector to secure the cable.
  • Page 23 LOOP A M-Bus A M-Bus A BMZ30 / M-BM M-Bus B M-Bus B NT V40-A3 +24 V BMZ-Module Alarm relay Failure relay Standard Standard R1 = 680 R2 = ∞ R3 = 0 R4 = ∞ HOTSPOT ADICOS HOTSPOT-1000 410-2410-001 EN11...
  • Page 24 NOTE! More information on how to install the ADICOS branching and connection box can be found in the GTE manual, no. 430-2410-001 5.3.4 Wiring Variations The actual wiring of the detector to the ADICOS branching and connection box can vary depending on the system configuration.
  • Page 25 X6ein (Al) ADICOS-AAB LOOP B LOOP B LOOP B LOOP A LOOP A LOOP A M-Bus A M-Bus A M-Bus B M-Bus B +24 V Detector with integrated ADICOS connection cable for detector FDnet or LSNi module ADICOS HOTSPOT-1000 410-2410-001 EN11...
  • Page 26 +24 V Primary cable Primary cable X7 (Stoer) X7 (Stoer) X6aus (Al) X6aus (Al) X6ein (Al) X6ein (Al) LOOP B LOOP B LOOP A LOOP A M-Bus A M-Bus A M-Bus B M-Bus B +24 V 410-2410-001 EN11 ADICOS HOTSPOT-1000...
  • Page 27: Commissioning

    The ADICOS HOTSPOT-1000 indicates a malfunction until the startup process is completed. ► Supply voltage to the device to start up the ADICOS HOTSPOT-1000. ► Start up the ADICOS system as described in the manual for the central unit used (ADICOS BMZ-30/M-Busmaster).
  • Page 28: Operation

    7.2.1 Fire Detection System Operation If the ADICOS HOTSPOT-1000 is connected to a fire panel, the alarm is transmitted to the fire panel via the fire detection system module. The fire detection system triggers the ADICOS HOTSPOT-1000 alarm. And the alarm relay is triggered and the red signal LED ADICOS HOTSPOT-1000 lights up.
  • Page 29 7.2.6 Day/Night Mode If the ADICOS HOTSPOT-1000 is operated in conjunction with a ADICOS BMZ-30, the fea- ture “Day/night mode” can be used. When the parameterization has been modified for this purpose in the ADICOS service software, the determination of whether an alarm is triggered is based on set 1 of the stored limit combinations during the day and set 2 at night.
  • Page 30: Maintenance

    Cleaning The ADICOS HOTSPOT-1000 may be cleaned with water and dishwashing liquid. Acids and bases may not be used; do not apply water pressure to clean. Always use a damp, soft cloth, never rough materials or sponges.
  • Page 31: Checking Signal Relay Functioning

    ATTENTION! Replace the ADICOS HOTSPOT-1000 no later than eight years after initial startup! 8.4.1 General Notes The ADICOS HOTSPOT-1000 has to be replaced with a similar detector or newer product version after eight years of operation. ADICOS HOTSPOT-1000 410-2410-001 EN11...
  • Page 32: Failure

    Failure Failure of the ADICOS HOTSPOT-1000 is indicated by the yellow signal LED lighting up as well as by the “Failure” signal relay deenergizing. The ADICOS HOTSPOT-1000 recognizes the following states and causes of failure:...
  • Page 33: 10 Technical Data

    200 nF Startup time (ready for operation) After about 10 seconds Resolution 32 x 31 pixels Capture angle 53° x 52° Reaction time < 1 second Temporal resolution 0.1 second or 1 second (depending on configuration) ADICOS HOTSPOT-1000 410-2410-001 EN11...
  • Page 34: 10.1 Measuring Range

    Such individual requests must be stated upon ordering so that they can be taken into consideration when calibrating the equipment and performing the production test. 10.2 Precision of Standard Version ADICOS HOTSPOT-1000 In regard to the precision of the temperature detection capacity of the ADICOS...
  • Page 35: 10.3 Purge Air Requirements

    Testing is advisable in severely turbulent air. 11 Disposal Return the device to the manufacturer when it reaches the end of its serviceable life. The manufacturer will ensure that the components are disposed of properly, in an environmen- tally friendly manner. ADICOS HOTSPOT-1000 410-2410-001 EN11...