Page 3
The ADICOS HOTSPOT-1000 is an IR fire detector used for optical and spatially resolved fire and heat detection. It is well suited for these applications: •...
The following types of notes are used through this manual: DANGER! This combination of symbol and signal word indicates an immediately danger- ous situation which could lead to death or severe injuries if it is not avoided. 410-2410-001 EN15 ADICOS HOTSPOT-1000...
Field Device Network (fire detection bus, SIEMENS fire detection systems) Local Security Network (fire detection bus, BOSCH fire detection systems) Fire detection system Storing this Manual Store this manual near the detectors, in a place where it can easily be accessed when needed for reference. ADICOS HOTSPOT-1000 410-2410-001 EN15...
Intended use also includes following the instructions in this manual and complying with all relevant local regulations. The ADICOS HOTSPOT-1000 may not be used for any other purpose. If the device is used in any other way, or if changes are made to the product, including in the course of installation and maintenance, the warranty claim is no longer valid.
• Only use original spare parts and original accessories! • Original spare parts and accessories may only be installed by trained spe- cialist personnel. • Qualified personnel are persons as described in Chap. 2.4 ADICOS HOTSPOT-1000 410-2410-001 EN15...
It is used for early and contact-free temperature and ember detection. Because of its dura- ble design, the ADICOS HOTSPOT-1000 can be used in adverse industrial environments. It is excellent for monitoring bulk goods prone to spontaneous combustion as well as conveyor systems.
3.3.1 Moving Objects Because of the fast response time of 100 milliseconds, the ADICOS HOTSPOT-1000 is ideal for monitoring of moving objects, e.g. transport and conveyor belts. Therefore, an early detection of pockets of ember transported on the conveyors can be realized.
Page 12
The purge air supply must remain uninterrupted as long as dust residue can be expected. The air flow rate can be restricted with throttle valves; one per detector, e.g. from the Festo series GR-QS4-LF, Festo art. no. 193966. 410-2410-001 EN15 ADICOS HOTSPOT-1000...
ADICOS System Software to be displayed. If the ADICOS HOTSPOT-1000 is connected to a fire panel with aid of an internal interface module, the fire panel controls the detector’s alarm display.
FUNCTIONING Standard configuration In the standard configuration, the temperature threshold of the ADICOS HOTSPOT-1000 is set to 60 °C. Individual modifications to configuration The ADICOS System Software can be used to change the limit of the ADICOS HOTSPOT-1000 irrespective of the standard (default) configuration upon delivery.
Chap. „11 Technical Data“). Dirt and condensation The ADICOS HOTSPOT-1000 is equipped with a purge air connection that prevents dusty air from polluting the optics. A detector heater is needed when there is a risk of condensation forming on the device.
Page 16
The ADICOS HOTSPOT-1000 must always have a clear, unobstructed view of the installation to be monitored. If the object to be monitored is obscured or is not within the visibility range of the ADICOS HOTSPOT-1000, the device will not be able to detect any heat sources and trigger an alarm.
Page 17
Certain disturbing influences can have a negative impact on the operation of the ADICOS HOTSPOT-1000, leading to a false alarm: - Direct sunlight and reflections due to reflective surfaces - Hot bodies (e.g. vehicle engines and exhaust systems) - Welding ADICOS HOTSPOT-1000 410-2410-001 EN15...
Attaching to a mounting bracket The ADICOS HOTSPOT-1000 is also available with a ball joint. The ball joint is connected to the detector with a angle bracket to the enclosure. There is a lever that can be released to adjust the detector to the proper angle, allowing it the best view of the detection area.
• Wiring may only be performed by specialist personnel! (–› Chap. 2.4, Per- sonnel qualification) • De-energize the entire detector system for any wiring! • Use ADICOS connection cables only for connecting detectors as well as ADICOS junction boxes! ADICOS HOTSPOT-1000 410-2410-001 EN15...
Page 20
Blue Fire panel interface A – in Violet Fire panel interface B – out Gray Fire panel interface A – out Blue/red M-Bus Max, 40 V, non-polarized Gray/pink With series resistor, standard 680 Ω 410-2410-001 EN15 ADICOS HOTSPOT-1000...
Page 21
The pre-alarm relay is linked to set 2 of the trigger limits. The pre-alarm functionality is en- sured as long as the limits programmed in set 2 are less sensitive than the limits in set 1. ADICOS HOTSPOT-1000 410-2410-001 EN15...
Page 22
INSTALLATION 5.3.2 Attaching ADICOS Connection Cable to ADICOS HOTSPOT-1000 Press the bayonet lock on the ADICOS connection cable against the detector connection. Carefully turn the entire bayonet lock to find the proper position for the twist protection. Firmly turn the bayonet ring on the connector to secure the cable.
Page 23
X6ein (Al) M-Bus LOOP B LOOP B M-Bus to next LOOP A LOOP A ADICOS-AAB M-Bus A M-Bus A M-Bus B M-Bus B ADICOS Power supply unit +24 V NT V40-A3 +40 V ADICOS-connection cable for detector ADICOS HOTSPOT-1000 410-2410-001 EN15...
Page 24
LOOP B LOOP B ADICOS-AAB LOOP B LOOP A LOOP A LOOP A M-Bus A M-Bus A M-Bus B M-Bus B +24 V Detector with integrated ADICOS connection cable for detector FDnet or LSNi module 410-2410-001 EN15 ADICOS HOTSPOT-1000...
Page 25
+24 V Primary cable Primary cable X7 (Stoer) X7 (Stoer) X6aus (Al) X6aus (Al) X6ein (Al) X6ein (Al) LOOP B LOOP B LOOP A LOOP A M-Bus A M-Bus A M-Bus B M-Bus B +24 V ADICOS HOTSPOT-1000 410-2410-001 EN15...
The plug connector for detector connection remains connected. Carefully pull off the old configuration module Insert the new configuration module in the correct orientation into the configuration module slot on the detector board Close the detector enclosure, required torque 1.5 Nm 410-2410-001 EN15 ADICOS HOTSPOT-1000...
NOTICE! The ADICOS detector indicates a malfunction until the startup process is com- pleted. Supply voltage to the device to start up the ADICOS HOTSPOT-1000. ► Start up the ADICOS system as described in the manual for the M-Busmaster interface ►...
7.2.1 Fire Detection System Operation If the ADICOS HOTSPOT-1000 is connected to a fire panel, the alarm is transmitted to the fire panel via the fire detection system module. The fire detection system triggers the ADICOS HOTSPOT-1000 alarm. The alarm relay is triggered and the red signal LED lights up. In case fire panel does not recognize to the alarm condition and does not respond the red LED flashes.
Page 29
7.2.5 Pre-alarm If the ADICOS HOTSPOT-1000 is equipped with a pre-alarm module and properly configured, set 2 of the saved limit combinations automatically acts as the trigger criterion for the pre- alarm. If the limits specified in set 2 are exceeded, the pre-alarm module relay switches and the red signal LED “Alarm”...
The ADICOS HOTSPOT-1000 may be cleaned with water and dishwashing liquid. Acids and bases may not be used; do not apply water pressure to clean. Always use a damp, soft cloth, never rough materials or sponges. The ADICOS HOTSPOT-1000 will not function correctly if it is not cleaned properly.
Replace the ADICOS HOTSPOT-1000 no later than eight years after initial start- 8.4.1 General Notes The ADICOS HOTSPOT-1000 has to be replaced with a similar detector or newer product ver- sion after eight years of operation. 8.4.2 Replacing the ADICOS HOTSPOT-1000 An old ADICOS HOTSPOT-1000 has to be replaced when •...
FAILURE Failure Failure of the ADICOS HOTSPOT-1000 is indicated by the yellow signal LED lighting up as well as by the “Failure” signal relay deenergizing. The ADICOS HOTSPOT-1000 recognizes the following states and causes of failure: Failure Description Measure Undervoltage / current...
The standard temperature detection range is 0 to 200 °C. The temperature ranges can be adjusted with aid of the ADICOS System Software. 11.3 Accuracy of Standard Version ADICOS HOTSPOT-1000 In regard to the precision of the temperature detection capacity of the ADICOS...
Class 3 (-20 °C dewpoint) Oil content Class 2 ( < 0.1 mg/m³) Required air flow rate In dusty, settled air > 2 l/min In dusty, flowing air > 8 l/min Testing is advisable in severely turbulent air. ADICOS HOTSPOT-1000 410-2410-001 EN15...