B16008-R0-160RC SERIES-U&C
See page 14 for information on interconnection.
Note: Wiring must be installed in compliance with local
regulations.
FOAM CEILING GASKET
Figure 3
Warning: Mixing the Live and Neutral connections when
interconnecting alarms will damage all the alarms - ensure
that the same colours are used throughout the premises
for Live, Neutral and Interconnect wires.
We strongly recommend that you check for the following
before connecting the alarm:
• check for Live and Neutral using a two probe tester.
• check for Live using a neon tester.
• check that the Interconnect wire is NOT connected to Live,
Neutral or Earth. Do not use an Earth wire for the
Interconnect line.
N.B. The alarm does not need to be earthed. However the terminal
marked
is provided for the convenience of the installer so that
any copper Earth wire or cable coloured green & yellow, can be
safely terminated.
To interconnect the Alarms connect all the IC terminals together
as shown in Figure 4 (see "Interconnecting Alarms" section
on page 14).
Figure 4
4. If the mains wires are recessed, bring the wires through the
rear hole in the mounting plate as shown in Figure 4.
17/1/07
11:13 AM
Page 11
INSERT SCREWDRIVER
TO LIFT AND REMOVE
WIRING COVER