VISTA-32FB/VISTA-128FB Programming Form

Some fields are programmed for each partition (shown as shaded fields). If you are programming a multiple-partition system,
see the Partition-Specific Fields section for programming these fields. Standard default (*97) values are shown in brackets [ ];
otherwise, default = 0.
*00
INSTALLER CODE
Enter 4 digits, 0-9 [5140]
*08
TEMPORAL SIREN PULSE
1=enable; 0=disable
*09
ENTRY DELAY #1
00, 02-15 times 15 seconds
Maximum "03" for UL Commercial Burglary installations.
*10
EXIT DELAY #1
00, 03-15 times 15 seconds
Maximum "04" for UL Commercial Burglary installations.
*11
ENTRY DELAY #2
00, 02-15 times 15 seconds (must be longer than Entry Delay
#1). Maximum "03" for UL Commercial Burglary installations.
*12
EXIT DELAY #2
00, 03-15 times 15 seconds (must be longer than Exit Delay
#1). Maximum "04" for UL Commercial Burglary installations.
*13
BELL 1 TIMEOUT
01-15 times 2 minutes. Minimum 16 minutes for UL
Commercial Burglary installations and minimum 6 minutes for
UL Commercial Fire installations
*15
KEYSWITCH ASSIGNMENT
Enter partition in which keyswitch used, 1-8; 9=silences
Notification Appliance Circuit if fire present; 0=disable
*16
BELL 1 CONFIRMATION OF ARMING DING [0]
1=enable; 0=disable.
Must be "1" for UL Commercial Burglary installations.
*17
AC LOSS KEYPAD SOUNDING
1=enable; 0=disable
*19
RANDOMIZE AC LOSS REPORT
1=10-40 min; 2= 6-12 hours; 0=normal report (about 2 min.
after AC loss).
Must be "2" for central and remote fire alarm systems.
*20
VIP MODULE PHONE CODE
Enter 01 - 09 for the first digit; enter
11 for "*" or 12 for "#" for the second digit.
Must be set to "0" for UL Commercial Burglary and UL
Commercial Fire installations.
*22
KEYPAD PANIC ENABLES
1=enable; 0=disable
*23
MULTIPLE ALARMS
1=enable; 0=disable
Must be "1" for UL Commercial Burglary installations
*24
IGNORE EXPANSION ZONE TAMPER
1=Ignore; 0=Enable tamper for RF and RPMs.
Must be "0" for UL Commercial Burglary and Commercial Fire
installations if using these devices.
| | |
*25
*26
[0]
|
[02]
*27
|
[03]
*28
|
[06]
|
[08]
*29
*30
|
[04]
*31
[0]
*32
*33
[0]
*34
[2]
|
|
[00],
[11]
*35
[001]
995
996
999
[1]
*36
[0]
– 5 –
BURG.TRIGGER FOR RESPONSE TYPE 8
1=enable; 0=disable
INTELLIGENT TEST REPORTING
1=enable (no report sent if any other report was recently sent);
0=disable (send report at programmed interval, field *27)
Must be "0" for UL Commercial Burglary and Commercial Fire
installations.
TEST REPORT INTERVAL
Enter interval in hours, 001-999; 000=no report;
Max. 024 for UL Commercial Burglary and Commercial Fire
installations.
POWER UP IN PREVIOUS STATE
1=enable; 0=disable
Must be "0" for UL Commercial Burglary and Commercial Fire
installations.
QUICK ARM
1=enable; 0=disable
MAIN DIALER TOUCHTONE OR ROTARY
1=TouchTone; 0=rotary
PABX ACCESS CODE
00-09; B-F (11-15)
PRIM. SUBS. ACCT #
Enter 00-09; B-F (11-15) [15 15 15 15]
PRIMARY PHONE NUMBER
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
SECONDARY PHONE NUMBER
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
DOWNLOAD PHONE NO.
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
DOWNLOAD ID NO.
|
|
|
|
Enter 00-09; A-F (10-15) [15 15 15 15 15 15 15 15]
[1]
[0]
]
| |
[024
[1]
[1]
[0]
|
|
|
|
|
|
|
|
|
|
|
|