Honeywell ADEMCO VISTA Series Programming Manual page 6

Commercial fire and burglary partitioned security system with scheduling
Hide thumbs Also See for ADEMCO VISTA Series:

Advertisement

*37
DOWNLOAD COMMAND ENABLES
0
Dlr Shtdwn Sys Shtdwn
Not Used Rmt Byp Rmt Disarm Rmt Arm Upld Pgm Dwnld Pgm
See field 1*53 for Callback disable option; [1=enable];
0=disable. For UL Commercial Burglary and Commercial Fire
installations, all entries must be "0."
*38
PREVENT ZONE XXX BYPASS
001-128; 00 if all zones can be bypassed
*39
ENABLE OPEN/CLOSE REPORT FOR
INSTALLER CODE
*40
OPEN/CLOSE REPORT FOR KEYSWITCH
1=enable; 0=disable
41
*
NORMALLY CLOSED or EOLR (Zones 3-8)
1=N.C.loops; 0=EOLR supervision.
Must be "0" for UL Commercial Burglary and Commercial Fire
installations.
*42
DIAL TONE PAUSE
0=5 seconds; 1=11 seconds; 2=30 seconds.
Must be "0" UL Commercial Burglary and Commercial Fire
installations.
*43
DIAL TONE DETECTION
1=wait for true dial tone; 0=pause, then dial
*44
RING DETECTION COUNT
01-14; 15=answering machine; 00=no detection.
Must be "00" for UL Commercial Burglary and Commercial Fire
installations.
*45
PRIMARY FORMAT
0=Low Speed; 1=Contact ID; 2=ADEMCO High Speed;
3= ADEMCO Express
*46
LOW SPEED FORMAT (Primary)
0= ADEMCO Low Speed; 1=Sescoa/Radionics
*47
SECONDARY FORMAT
0=Low Speed; 1=Contact ID; 2= ADEMCO High Speed;
3= ADEMCO Express
*48
LOW SPEED FORMAT (Sec.)
0= ADEMCO Low Speed; 1=Sescoa/Radionics
*49
CHECKSUM VERIFICATION
1=enable; 0=disable
*50
SESCOA/RADIONICS SELECT
1=Sescoa; 0=Radionics
*51
DUAL REPORTING
1=yes; 0=no If used with Spilt Reporting "1" option (1*34),
alarms and alarm restores go to both primary & secondary
numbers, while all other reports go to secondary only. If used
with Split Reporting "2" option, alarms and alarm restores go
to both, open/close and test messages go to secondary only,
while all other reports go to primary. If used with Split
Reporting "3" option, fire alarms and fire supervisory signals
go to both, all other reports go to secondary only.
*52
STANDARD/EXPANDED REPORT FOR PRIMARY
[0 0 0 0 0 0]
Alarm
Rstr
0=standard; 1=expanded;
Note: Expanded overrides 4+2 format.
| |
[000]
[1]
1=enable; 0=disable
[0]
[0]
[0]
[1]
[00]
[0]
[0]
[0]
[0]
[0] [0]
Prim
[0]
[0]
Byp
Trbl
O/C
LoBat
*53
STANDARD/EXPANDED REPORT FOR SECONDARY
[0 0 0 0 0 0]
0=standard; 1=expanded;
Note: Expanded overrides 4+2 format.
*56
DYNAMIC SIGNALING DELAY
Select the delay time (00-15) times 15 seconds before sending
to second destination.
*57
DYNAMIC SIGNALING PRIORITY
0=Primary dialer; 1=LRR, as first reporting destination.
*58
LRR CENTRAL STATION #1 CATEGORY ENABLE
[0 0 0 0 0 0]
0=disable, 1=enable for reports for primary subs ID of LRR
*59
LRR CENTRAL STATION #2 CATEGORY ENABLE
[0 0 0 0 0 0]
0=disable, 1=enable for reports for secondary subs ID of LRR
*64
PAGER INSTALLED
0=No, 1=Yes, alpha numeric pager interface is installed.
*65
PAGER PHONE # FOR ALARMS
|
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
*66
PAGER ID # FOR ALARMS
Enter up to 10 digits for the pager id #
*67
PAGER PHONE # FOR SUPERVISION
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
*68
PAGER ID # FOR SUPERVISION
Enter up to 10 digits for the pager id #
*69
PAGER PHONE # FOR BYPASSES
Sec
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
*70
PAGER ID # FOR BYPASSES
Enter up to 10 digits for the pager id #
*71
PAGER PHONE # FOR OPENS/CLOSES
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
– 6 –
Alarm Rstr
Byp
Trbl
O/C LoBat
Alarm Trbl
Byp
O/C
Syst
Alarm Trbl
Byp
O/C
Syst
|
[00]
[0]
Test
Test
[0]