Advant Controller 450 Product Guide
Chapter 5 Mechanical Design
5-4
Advant Controller 450 with S100 I/O in RM500V2 Cabinets
The delivery is assembled in up to six cabinets, for the controller subrack and the five
possible I/O subracks that can be connected to the same bus extension.
With the cabinet housing the controller subrack to the left, the building direction is to
the right.
Cabinet no 2, 4 and 6 contain no hinged frame.
Modems are always placed in cabinet no 1 in a modem subrack. For maximum four
modems, mounting plates to the left of the controller subrack is used.
All cabinets that share the same S100 I/O bus extension (max 12m) are connected to
the same power switch placed in the cabinet housing the controller subrack.
Cabinet no. 1, 3 and 5 have their own power supplies (power switch in cabinet no 1).
One set of power supplies for field equipment, if ordered, is placed in cabinet no 2.
Connection units are placed only within the same single or double cabinet that houses
the corresponding I/O subrack or in the next cabinet to the right.
The boards are placed in the I/O subracks in the order AI, AO, DO, DI starting in subrack
no 1.
DI boards are the last group. Connection units for higher voltage than 24 V
occupies more space than the corresponding units for 24 V.
1
CTR
I/O 1
PS
SW
Mains
Figure 5-3. Maximum cabinet configuration for Advant Controller 450 with S100 I/O
NOTE
2
3
4
I/O 2
I/O 3
PS
Conn.
units
PS Power Supply
SW Power Switch
assembled in RM500V2 cabinets
5
6
I/O 4
I/O 5
PS
3BSE 015 953R201 Rev B