1.Airflow based upon dry coil at 230v with factory-approved filter and electric heater (2 element heater sizes 1800 through 3600, 3 element heater sizes 4200 through 6000). For FEM4X,
FEM4P, and REM4X models, airflow at 208 volts is approximately the same as 230 volts because the ECM motor is a constant torque motor. The torque doesn't drop off at the speeds the
motor operates.
2.To avoid potential for condensate blowing out of drain pan prior to making drain trap:
Return static pressure must be less than 0.40 in. wc.
Horizontal applications of 4200 - 6000 sizes must have supply static greater than 0.20 in. wc.
3.Airflow above 400 cfm/ton on 4800 - 6000 size could result in condensate blowing off coil or splashing out of drain pan.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Table 5 – Electric Heater Static Pressure Drop (in. w.c.)