SECTION 5: DETECTOR CABLE WIRING
Table 1: Pigtail Wiring Data
Wire
Wire
Color
Number
1
BLACK
4
RED
2
GREEN
3
WHITE
5
GRAY
6
PURPLE
7
BROWN
9
BLUE
8
BROWN /
WHITE
BLUE /
10
WHITE
11
YELLOW
13
ORANGE
12
YELLOW
/ BLACK
14
ORANGE
/ BLACK
None
Non-
isulated
Wire
Note: The Fire ALERT and ALARM relay loop-through contacts may be used for End-of-Line
(EOL) resistors for supervision of contact wiring.
Warrantee
The Control Panel is warranted for two years against defects in materials and
Workmanship.
24 V Return (-) Supply
+ 24 VDC Supply
FireBus RS-485 Digital Data A Signal
FireBus RS-485 Digital Data B Signal
Fault Relay Terminal A, Contact to B during Normal Operation
Fault Relay Terminal B, Contact to A during Normal Operation
Fire ALARM Relay Terminal A
Fire ALARM Relay Terminal B
Fire ALARM Relay Terminal A loop-through
Fire ALARM Relay Terminal B loop-through
Fire ALERT Relay Terminal A
Fire ALERT Relay Terminal B
Fire ALERT Relay Terminal A loop-through
Fire ALERT Relay Terminal B loop-through
Cable shield – To be terminated at the Fire Alarm Panel Chassis
Ground.