Start Charge Configuration

Charge Delay

Charge Delay Type:
-
OFF (no delay)
-
Charge Delay Time of Day
-
Time After Battery Connect
Charge Delay On Days: Selects day or days of the week to delay charge. One or more days may be
selected, or none.
Charge Delay Time of Day: Charge will not start until the time of day stored in VALUE (24 Hour format) is
reached.
Delay Time After Battery Connection: Start of charge is delayed by the amount of time stored in
VALUE (0 to 24 Hours).

Charge Blockout

Blockout Days: Selects day or days of the week to block out charge. One or more days may be selected,
or none.
Blockout Start Time: Sets block out start time.
Blockout End Time: Sets block out end time.
Conditional Charge %
Set conditional charge %. The charger will only charge if the battery has reached the limit of depth of
discharge (DoD) of more than x%. For example if the user wants to charge the battery only if it is discharged
more than 30%, the parameter 30 has to be entered in the conditional charge. The 0 value disables the
function.

Opportunity Daily Charge

Start Daily Charge Time: Sets daily charge start time.
End Daily Charge Time: Sets daily charge end time.

Fast Voltage Regulation

This is only accessible through high level password. If you do have access to this setting make sure you
understand what you are doing. If adjusted incorrectly it could eventually damage a battery if not corrected.
Enter value between 2450 and 2750 in mVPC. Usually not
necessary to change. Factory default is 2650.
erord

Post Charge Configuration

Cool Down ON/OFF

Turns the cool down ON or OFF.

Cool Down Time

Sets the period of cool down time.