Hawker EnerSys LifeSpeed IQ Safety And Use Instructions
Hawker EnerSys LifeSpeed IQ Safety And Use Instructions

Hawker EnerSys LifeSpeed IQ Safety And Use Instructions

3-phase chargers

Advertisement

Quick Links

Safety and use instructions LifeSpeed IQ
SAFETY INSTRUCTIONS
GOALS OF THIS MANUAL
This manual is aimed at any authorized personnel wanting
to use a 3-phase LifeSpeed IQ
acid motive power batteries (vented, Hawker XFC
Water Less
®
/Water Less
®
20 ranges)
This manual contains information on:
Charger functionality.
Use and setting of charger parameters.
Technical specifications of the LifeSpeed IQ chargers.
EnerSys
®
intends to provide clear and simple information
in this manual, and assumes no responsibility for misunder-
standing or improper interpretation of the information.
The owner of the equipment is required to preserve this
manual during the life of the equipment and to transfer said
manual to any subsequent purchaser.
WARRANTY
Warranty is offered by the manufacturer based on local
regulations. Please contact your local distributor for further
information.
RECOMMENDATIONS
Recommendations for safe operation
This manual should be carefully read, prior to using the
equipment, by anyone intending to use the charger.
The LifeSpeed IQ:
Must not have its air circulation impaired in any way,
primarily around the air inlet areas.
Dust accumulation must be removed every 12 months.
Must be used within its protection norms, and never
be directly in contact with water.
Must be used only within the temperature range
specified in the technical specifications.
Internal connection torques must be checked once a
year.
Must not be installed on a surface subject to high
vibration levels (proximity of motors, compressors, etc.).
Must not be installed close to the batteries in order to
avoid any gassing that could damage it prematurely.
Must not be installed in arduous environments such as:
• Harbour applications (saline environment)
• Close to cold stores
• External locations with exposure to wind and rain
Operator safety
All proper precautions must be observed when the
equipment is used in areas where accidents are possible.
Ensure proper ventilation when the charger is used with
lead-acid batteries, due to gassing. Never disconnect the
battery during the charging process.
General warnings
Requirements for use:
The equipment must be properly grounded (earthed).
The input voltage must match the charger requirements.
The battery voltage must match the charger's
capabilities.
The battery capacity is within the charger's range.
ELECTRICAL SAFETY
Safety regulations and requirements must be observed.
Safety devices installed on the electrical supply to the
chargers must be of the proper type and rating. It is
important to ensure that only fuses of the proper
capacity should be used if they need to be replaced.
TM
- 3-phase chargers
charger to recharge lead
TM
TM
, Gel or
The equipment must be totally disconnected from all power
sources (mains supply and battery) before it can be opened
for inspection or servicing. The battery can only be discon-
nected after the charge has been stopped by pushing the
Stop/Start button. Access to the inside of the charger
should be restricted to authorized maintenance personnel.
Please consult a qualified factory representative about any
problems or questions related to the installation of this
unit.
LIMITS OF USE
This charger is designed to be used in a sheltered area.
It is designed exclusively to recharge lead batteries in an
industrial environment.
PRODUCT RECYCLING - DESTRUCTION
When this charger becomes obsolete, it can be recycled
or destroyed by authorized facilities. Local regulations will
prevail and must be followed.
MODIFICATIONS AND IMPROVEMENTS
EnerSys reserves the right, at any time, to modify or
improve its products, without any obligation to update
this product or this manual accordingly.
The customer is not permitted to modify the product from
its original design and configuration (e.g. fitting additional
modules).
Any changes made by the customer could affect the
product performance and invalidate the warranty.
RECEIVING - STORAGE
Upon receipt, please inspect visually the exterior of the
charger for any physical damage. If necessary, proceed
within 24 hours with the usual claims procedure with the
transport company.
If the charger is to be stored before use, it should remain
in the original packaging, carefully closed. Store in a clean,
dry area at a moderate temperature (0 °C to +40 °C). If the
equipment is stored at a temperature below 15°C, it must
be gradually (24 hours) restored to operating temperature
before use, to prevent the risk of condensation that could
cause electrical faults and short-circuits.
INFORMATION PLATE
Located on either side of the charger.
EC DECLARATION OF CONFORMITY
EnerSys hereby declares that the chargers in the
LifeSpeed IQ range covered by this declaration
conform to European Directives:
Directive 2006/95/EC (Low Voltage Directive):
EN60950-1
Directive 2004/108/EC (ElectroMagnetic Compatibility):
EN61000-6-2, EN61000-6-4:
Immunity and emissions limits for industrial electronics
(class A- Industrial Environments)
Directive 2002/95/EC (RoHS)
ENGLISH

Advertisement

loading

Summary of Contents for Hawker EnerSys LifeSpeed IQ

  • Page 1 This manual is aimed at any authorized personnel wanting should be restricted to authorized maintenance personnel. to use a 3-phase LifeSpeed IQ charger to recharge lead acid motive power batteries (vented, Hawker XFC , Gel or Please consult a qualified factory representative about any Water Less ®...
  • Page 2 Start/End of list (Press 2 seconds) and very effectively analyses its condition for optimum handling. Several charging profiles are available (vented The central button is equipped with lead/acid batteries, Hawker batteries, gel batteries a two-coloured LED Green/Red ® or Water Less ®...
  • Page 3: Charging The Battery

    Starting the charge MODULES MANAGEMENT 1. If Autostart is On (default ON), the charge starts auto- matically when the battery is connected to the charger. • There are two types of the modules: 24/36/48V and To stop the charge, press the central button 72/80V.
  • Page 4 2. If an equalisation charge has been programmed (vented battery), it will start automatically. Alternatively, an equalisation charge can be triggered manually; go to section End of charge with equalisation . 3. Press the central button or disconnect the battery that is now ready for use.
  • Page 5: Messages And Fault Codes

    MESSAGES AND FAULT CODES Fault Cause Solution Critical battery Wait until the battery TEMP* temperature. temperature cools DF1* Charger or mains DF1 appears when down, check the battery supply problem. the charger is not able state (water, profile) to supply its output current.