Codes And Standards - Bryant 935SB Installation, Operating And Maintenance Instruction

Single-stage, upflow/horizontal ultra low nox, 35-in. tall, condensing gas furnace
Table of Contents

Advertisement

935SB: Installation, Start-up, Operating and Service Maintenance Instructions
This furnace is designed for minimum continuous return-air temperature
of 60°F (15°C) db or intermittent operation down to 55°F (13°C) db such
as when used with a night setback thermostat. Return-air temperature
must not exceed 80°F (27°C) db. Failure to follow these return-air
temperature limits may affect reliability of heat exchangers, motors, and
controls (see
Fig.
3).
Fig. 3 – Freeze Protection and Return Air Temperature
The furnace should be sized to provide 100 percent of the design heating
load requirement plus any margin that occurs because of furnace model
size capacity increments. None of the furnace model sizes can be used if
the heating load is less than half of the furnace model's output capacity.
Use Air Conditioning Contractors of America (Manual J and S);
American Society of Heating, Refrigerating, and Air-Conditioning
Engineers; or other approved engineering method to calculate heating
load estimates and select the furnace. Excessive oversizing of the
furnace may cause the furnace and/or vent to fail prematurely, customer
discomfort and/or vent freezing.
Failure to follow these guidelines is considered faulty installation and/or
misapplication of the furnace; and resulting failure, damage, or repairs
may impact warranty coverage.
For accessory installation details, refer to the applicable instruction
literature.
NOTE: Remove all shipping materials, loose parts bags, and literature
before operating the furnace
(Table
furnaces also contain an additional parts bag for the condensate trap, see
Condensate Trap section.
Table 3 – Loose Parts Bag
DESCRIPTION
Air Intake Pipe Flange
Vent Pipe Flange
Pipe Flange Gaskets
Sharp Tip Screws (Vent and Inlet Flanges)
Vent Pipe Coupling
Vent Pipe Coupling Clamps
Gas Line Grommet
Junction Box Cover
Junction Box Base
Green Ground Screw
Blunt Tip Screws (Junction Box)
Thermostat Wire Grommet
Rubber Drain Elbow
Drain Tube Clamps
1/2-in. CPVC to 3/4-in. PVC Pipe Adapter
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
A150573
3). The Ultra Low NOx condensing
QTY
1
1
2
10
1
2
1
1
1
1
3
1
1
2
1
NOTE: Downflow not permitted with any return air configuration.
Fig. 4 – Prohibited Installations
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death
and/or property damage.
Do not install the furnace on its back or hang furnace with control
compartment facing downward. Safety control operation will be
adversely affected. Never connect return-air ducts to the back of the
furnace (see
Fig.
4).
Fig. 5 – Installation in a Garage

CODES AND STANDARDS

Follow all national and local codes and standards in addition to these
instructions. The installation must comply with regulations of the
serving gas supplier, local building, heating, plumbing, and other codes.
In absence of local codes, the installation must comply with the national
codes listed below and all authorities having jurisdiction.
In the United States, follow all codes and standards for the following:
6
WARNING
18-IN. (457.2 mm)
MINIMUM TO BURNERS
A190256
A93044