Tyco DS-1 Series Manual
Tyco DS-1 Series Manual

Tyco DS-1 Series Manual

Dry type sprinklers
Hide thumbs Also See for DS-1 Series:

Advertisement

Quick Links

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Series DS-1 — 5.6 K-factor
Dry Type Sprinklers
Standard Response, Standard Coverage
General
Description
The Tyco
Series DS-1, 5.6 K-factor,
®
Standard Response, Standard Cover-
age, Dry Type Sprinklers are decorative
5 mm glass bulb automatic sprinklers
designed for the following typical uses:
• where pendent sprinklers are re-
quired on dry pipe systems that are
exposed to freezing temperatures
(e.g. sprinkler drops from unheated
portions of buildings)
• where sprinklers and/or a portion
of the connecting piping may be
exposed to freezing temperatures
(e.g. sprinkler drops from wet sys-
tems into freezers, sprinkler sprigs
from wet systems into unheated
attics, or horizontal piping exten-
sions through a wall to protect an
unheated area of a building)
• where sprinklers are used on sys-
tems that are seasonably drained
to avoid freezing (e.g. vacation re-
sort areas)
WARNINGS
The Series DS-1 Dry Type Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page  of 8
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these
devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
The Series DS-1 Dry Type Sprinklers
must only be installed in fittings that
meet the requirements of the Design
Criteria section.
Model/Sprinkler
Identification
Numbers
TY3255 - (Pendent)
TY3155 - (Upright)
TY3355 - (Horizontal Sidewall)
Technical
Data
Approvals
UL and C-UL Listed.
FM and NYC Approved.
(Refer to Table A)
Maximum Working Pressure
175 psi (12,1 bar)
Inlet Thread Connection
1 inch NPT (Standard Order)
ISO 7-R1
Discharge Coefficient
K = 5.6 GPM/psi
1/2
(80,6 LPM/bar
1/2
)
Temperature Ratings
Refer to Table A
Finishes
Sprinkler: Natural Brass, Chrome
Plated, White Polyester
Escutcheon: White Coated or Chrome
Plated, Brass Plated
JANUARY, 2008
Physical Characteristics
Inlet. . . . . . . . . . . . . . . . . . . . . Copper
Plug . . . . . . . . . . . . . . . . . . . . Copper
Yoke . . . . . . . . . . . . . . Stainless Steel
Casing . . . . Galvanized Carbon Steel
Insert . . . . . . . . . . . . . . . . . . . Bronze
Bulb Seat . . . . . . . . . . Stainless Steel
Bulb . . . . . . . . . . . . . . . . . . . . . .Glass
Compression Screw . . . . . . . . Bronze
Deflector. . . . . . . . . . . . . . . . . Bronze
Frame . . . . . . . . . . . . . . . . . . . Bronze
Guide Tube . . . . . . . . . Stainless Steel
Water Tube . . . . . . . . . Stainless Steel
Spring . . . . . . . . . . . . . Stainless Steel
Sealing Assembly . . . . . . . . . . . . . . . .
. . . . . . . . . .Beryllium Nickel w/Teflon*
Escutcheon . . . . . . . . . . Carbon Steel
*Registered Trademark of DuPont
Patents
U.S.A. Patent No. 5,188,185
TFP500

Advertisement

Table of Contents
loading

Summary of Contents for Tyco DS-1 Series

  • Page 1 Failure to do so may Description impair the performance of these devices. The Tyco Series DS-1, 5.6 K-factor, ® The owner is responsible for maintain- Standard Response, Standard Cover- ing their fire protection system and de- age, Dry Type Sprinklers are decorative vices in proper operating condition.
  • Page 2 Page 2 of 8 TFP500 SPRINKLER FINISH TY3255 Pendent TY3255 Pendent TY3355 Hor. Sidewall w/ Standard w/ Std. Escutcheon with top of Recessed Escutcheon (Ref. Fig. 5) Deflector-to-Ceiling (Ref. Fig. 3) w/ Deep Escutcheon distance of w/ Wide Flange (Ref. Fig. 6) 4 to 12 inches Recessed Escutcheon w/o Escutcheon...
  • Page 3 TFP500 Page  of 8 SPRINKLER FITTING SPRINKLER FITTING SPRINKLER FITTING (REFER TO DESIGN (REFER TO DESIGN (REFER TO DESIGN CRITERIA SECTION) CRITERIA SECTION) CRITERIA SECTION) FACE OF FACE OF FACE OF SPRINKLER SPRINKLER SPRINKLER FITTING FITTING FITTING ORDER LENGTHS: ORDER LENGTHS: ORDER LENGTHS: 3-1/2"...
  • Page 4: Operation

    TY3355 hORIZONTAL SIDEWALL w/ STANDARD ESCuTChEON Design Criteria ORDER LENGTHS: FACE OF 1/2" to 45-3/4" (12,7 to 1162,1 mm) MOUNTING The Tyco ® Series DS-1 Sprinklers are IN 1/4" (6,4 mm) INCREMENTS SURFACE intended for use in fire sprinkler sys- 4-13/16" ± 1/8"...
  • Page 5 TFP500 Page 5 of 8 reducing tee’s when locating the DS- STRAP TIES 1 Sprinklers directly below the branch (ENDS ON TO WET SIDE line. Otherwise, use the configuration OPPOSING SYSTEM OUTLET shown in Figure 13 to assure complete SIDES OF PLUGGED drainage of water from above the DS-1 BOOT)
  • Page 6: Installation

    Refer to the Design Criteria section for Automatic sprinkler systems should be other important requirements regard- The Tyco Series DS-1 Dry Type Sprin- inspected, tested, and maintained by a ® ing piping design and sealing of the...
  • Page 7: Limited Warranty

    TFP500 Page  of 8 Limited Ordering Warranty Procedure Products manufactured by Tyco Fire Dry Sprinklers: & Building Products (TFBP) are war- Contact your local distributor for ranted solely to the original Buyer for availability, and please specify the ten (10) years against defects in mate-...
  • Page 8 * Eastern Hemisphere sales only. TABLE B PART NuMBER SELECTION SERIES DS-1, STANDARD RESPONSE, STANDARD COVERAGE, DRY TYPE SPRINKLERS (use Prefix “I” for ISO 7-R1 Connection, e.g., I-60-961-1-180) © 2007-2008 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale Pennsylvania 19446...

This manual is also suitable for:

Ty3255Ty3155Ty3355

Table of Contents