Stainless steel dry-type sprinklers
Hide thumbs Also See for DS-1 Series:

Advertisement

Series DS-1 Stainless Steel Dry-Type Sprinklers
5.6K Pendent, HSW, and Extended Coverage HSW
Standard and Quick Response
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/tfp560
General
Description
TYCO Series DS-1 Stainless Steel Dry-
Type Sprinklers, 5.6K Pendent, Hori-
zontal Sidewall (HSW), and Extended
Coverage HSW, Standard (5 mm bulb)
and Quick (3 mm bulb) Response are
the first stainless steel dry-type sprin-
klers to be listed by UL and C-UL. With
a K-factor of 5.6, these corrosion-resis-
tant automatic sprinklers can be used
in wet-pipe, dry-pipe, or preaction
systems.
These pendent and horizontal sidewall
sprinklers are available in a variety of
configurations to suit coverage type
and thermal sensitivity. For details, see
Page 1 of 10
the Sprinkler Identification Numbers
(SINs) section.
Series DS-1 Stainless Steel Dry-Type
Sprinklers are typically used in the fol-
lowing applications:
Where corrosive atmospheres exist,
for example, salt-water areas, parking
garages, chemical storage areas,
mechanical rooms, industrial manufac-
turing sites, and software chip washing
facilities
• Dry-pipe
systems
exposed
freezing temperatures, for example,
sprinkler drops from unheated
portions of buildings
• With pipe connections exposed to
freezing temperatures, for example,
sprinkler drops from wet-pipe
systems into freezers or hori-
zontal piping extensions to protect
unheated areas
• In
systems
that
are
ably drained to avoid freezing, for
example, vacation areas
The stainless steel construction of
these sprinklers extends the life of a
sprinkler beyond that of traditional
copper alloy sprinklers exposed to
corrosive atmospheres. Although
corrosion-resistant sprinklers have
passed the standard corrosion tests of
the applicable approval agencies, the
testing is not representative of all pos-
sible corrosive atmospheres.
Consequently, it is necessary that the
end user be consulted with respect to
the suitability of this alternate material
of construction for any given corrosive
environment. As a minimum, consider
the following criteria:
• Ambient temperature
• Concentration of chemicals
• Humidity
• Gas/chemical velocity
• Corrosive nature of the chemical to
which the sprinklers are exposed
Pendent
The pendent sprinklers are provided
with stainless steel escutcheons that
allow vertical adjustment during instal-
lation. This adjustment provides a
measure of flexibility in determining the
MAY 2024
Worldwide
www.tyco-fire.com
Contacts
to
length of fixed piping to cut for sprin-
season-
kler drops.
Horizontall Sidewall
The horizontal sidewall sprinklers are
designed for installation along a wall
or side of a soffit and just beneath a
smooth ceiling. Sidewall sprinklers are
commonly used instead of pendent
sprinklers due to aesthetics or build-
ing construction considerations where
piping along the ceiling is not desirable.
NOTICE
The Series DS-1 Stainless Steel Dry-
Type Sprinklers described herein must
be installed and maintained in compli-
ance with this document, as well as
with the applicable standards of the
NATIONAL FIRE PROTECTION ASSO-
CIATION (NFPA), in addition to the
standards of any authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
The Series DS-1 Stainless Steel Dry-
Type Sprinklers must only be installed
in fittings that meet the requirements of
the Design Criteria section.
TFP560

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DS-1 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco DS-1 Series

  • Page 1 As a minimum, consider NATIONAL FIRE PROTECTION ASSO- the following criteria: TYCO Series DS-1 Stainless Steel Dry- CIATION (NFPA), in addition to the • Ambient temperature Type Sprinklers, 5.6K Pendent, Hori- standards of any authorities having zontal Sidewall (HSW), and Extended jurisdiction.
  • Page 2: Technical Data

    Sprinkler Operation Maximum Working Pressure 175 psi (12,1 bar) Identification Inlet Thread Connections When TYCO Series DS-1 Stain- less Steel Dry-Type Sprinklers, 5.6K 1-Inch NPT or ISO 7-R 1 Numbers (SINs) Pendent, Horizontal Sidewall (HSW), Discharge Coefficient and Extended Coverage HSW, Stan- K=5.6 gpm/psi...
  • Page 3 TFP560 Page 3 of 10 Standard Coverage Extended Coverage Horizontal Sidewall Pendent Horizontal Sidewall TY3230 TY3250 TY3337 TY3357 TY3339 3 mm Bulb 5 mm Bulb 3 mm Bulb 5 mm Bulb 3 mm Bulb with Standard with Standard* with Standard with Standard with Standard Escutcheon...
  • Page 4 60°F However, the use of the Figure 730 Tee Exposed to (4°C) (10°C) (16°C) for this arrangement is limited to wet- TYCO Series DS-1 Stainless Steel Discharge pipe systems. Minimum Exposed Dry-Type Sprinklers, 5.6K Pendent, End of Barrel Length², Sprinkler...
  • Page 5: Installation

    With the sprin- eon plate by under- or over-tightening TYCO Series DS-1 Stainless Steel Dry- kler held horizontally, a small air bubble the sprinkler. Re-adjust the position of Type Sprinklers, 5.6K Pendent, Hori- should be present.
  • Page 6 TFP560 Page 6 of 10 SPRINKLER FITTING SPRINKLER FITTING (REFER TO DESIGN (REFER TO DESIGN CRITERIA SECTION) CRITERIA SECTION) FACE OF FACE OF SPRINKLER SPRINKLER FITTING FITTING ORDER LENGTHS: ORDER LENGTHS: 3-3/4" to 48" 2-3/4" to 48" 1-3/4" DIA. (95,3 to 1219,2 mm) (69,9 to 1219,2 mm) (44,5 mm) IN 1/4"...
  • Page 7 TFP560 Page 7 of 10 ORDER LENGTHS: 2-3/8" ± 1/8" 2-3/4" to 48" (60,3 ± 3,2 mm) 3" DIA. FACE OF FACE OF (69,9 to 1219,2 mm) (76,2 mm) SPRINKLER MOUNTING IN 1/4" (6,4 mm) FITTING SURFACE INCREMENTS 5/16" 3.5° (7,9 mm) SPRINKLER FITTING 1-3/4"...
  • Page 8: Care And Maintenance

    TY3250 – Standard Response in compliance with this document, as well as with the applicable standards Standard Coverage TYCO Series DS-1 Stainless Steel of the NATIONAL FIRE PROTECTION Horizontal Sidewall Dry-Type Sprinklers, 5.6K Pendent, ASSOCIATION such as NFPA 25, in TY3337 –...
  • Page 9 TFP560 Page 9 of 10 P/N* 60 – XXX – X– XXX Pendent Order Quick Response, Standard Coverage Length Figure 1 in. NPT Examples Standard Escutcheon 5.50 in. Recessed Escutcheon 8.25 in. TY3230 Deep Escutcheon 18.00 in. Without Escutcheon 18.75 in. 37.25 in.
  • Page 10 TFP560 Page 10 of 10 1467 Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220 © 2024 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;...