Package Contents; Handling Instructions; Removing The Packaging; Appliance Preparation - ACV WaterMaster 25 Evo Installation Operation & Maintenance

Hide thumbs Also See for WaterMaster 25 Evo:
Table of Contents

Advertisement

PACKAGE CONTENTS

At product reception and after removal of
packaging, check the package contents and
that the appliance is free of damages.
WaterMaster Evo water heater
Installation, Operation and Maintenance Instructions
Orifice for the natural gas to propane conversion
+ stickers (Except in Belgium)
Ball condensate trap to be installed.
A primary safety valve Ø 1/2" (F) to be installed

HANDLING INSTRUCTIONS

The appliance weighs more than 180 kg,
which could present a risk of injury. Ask for
help to handle it and use an appropriate
lifting means.
If using a pallet truck to transport the
appliance, remove the bottom front panel
(see ML booklet for instructions).
Bring the appliance as close as possible to
the installation location before removing the
packaging.
If necessary and to make transport easier,
the appliance casing can be removed for
transportation to the final installation location.
Refer to ML booklet for the correct procedure.
Before removing the packaging, ensure that
the installation area is clear and that there
are no obstacles making the handling and
installation difficult or unsafe.

REMOVING THE PACKAGING

1. Remove the plastic wrapping.
2. Remove the protection pieces and discard in ac-
cordance with applicable local regulations.

APPLIANCE PREPARATION

Remove
the
bottom
panel stored at the
back of the appliance
for transport. Install on
the appliance when it is
in its final position. Refer
to the ML Booklet for
the correct installation
procedure.
Perform the gas conver-
sion to propane as re-
quired. Refer to "Conver-
sion to Propane" on page 30.
Install the optional filling kit (accessory). Please
contact your ACV representative for more infor-
mation.
26
Installation
Close the circulation tube end tap (1) (access
from the bottom of the appliance)
The circulation tube is equipped with an
end tap that is open when the appliance is
delivered (to prevent test water from being
stuck in the circuit and freezing during
transport). Make sure that you close the tap
before filling the system with water.
Install the ball condensate trap, then the bottom
front panel (to be clipped in)
Fit the condensate trap, complete with the
ball, making sure to install the items in the
correct sequence and connect the hose to
the drain using a connection that can be
inspected. Fill the trap with clean water.
Make sure to prevent the condensates from
freezing. Refer to the procedure provided
with the condensate trap, or get it from
www.acv.com (See
with QR code)
Install the safety valve kit : primary circuit safety
valve at the back of the appliance
A1009341-664Y8300 • B
1
for an access
page 4
EN

Advertisement

Table of Contents
loading

Table of Contents