Installation, operating and
maintenance instructions
BNE 1 - BNE 2 - BNE 3
excellence in hot water
28/10/2004 - 66401200

Advertisement

Table of Contents
loading

Summary of Contents for ACV BNE 1

  • Page 1 Installation, operating and maintenance instructions BNE 1 - BNE 2 - BNE 3 excellence in hot water 28/10/2004 - 66401200...
  • Page 3: Table Of Contents

    INDEX INTRODUCTION BURNER CHARACTERISTICS Who should read these instructions Description of the burner Symbols Factory setting parameters Applicable standards Burner dimensions Important notes COMMISSIONING AND MAINTENANCE USER GUIDE Filling the hot water and heating circuits Use of the boiler Using the boiler for the first time Setting the burner to safety mode Servicing recommendation Boiler maintenance...
  • Page 4: Introduction

    If the problem persists, call an engineer. The pressure should not fall below 1 bar. If it does, refer to the paragraph ACV declines all liability for any damage caused as a result of entitled “Gauge pressure in the heating system”, later in this section.
  • Page 5 Your system must be equipped with a heating safety valve calibrated to 3 bar. SETTING THE ACV BURNER TO SAFETY MODE Ensure that the system is always under water pressure. When the system is cold and the air inside it has been vented, the gauge must If the burner is not working: indicate a pressure of between 1 and 1.5 bar, depending on the...
  • Page 6: Description

    • The boiler may be connected directly to the chimney using a B23 BOILER VIEWS AND KEY TO PARTS chimney connection. 1. Cold water inlet • Model BNE 1: output between 20 and 25 kW. 2. Hot water thermostat pocket 3. Hot water outlet 4. Steel outer tank •...
  • Page 7: Technical Characteristics

    - Heating circuit: 4.5 bar purposes: - Hot water circuit: 13 bar Operating temperature DIMENSIONS - Maximum temperature: 90°C Ø D Ø Kg (*) BNE 1 1505 1390 BNE 2 1570 1450 BNE 3 1610 1475 The weights shown are drained weights.
  • Page 8: Installation

    The attendant risk of condensation may cause damage ventilation requirements according to Belgian regulations. to some chimneys. To avoid this risk we strongly advise that you line the chimney. Please contact your installer for further details BNE 1 BNE 2 BNE 3 about this. Ventilation Min.
  • Page 9: Heating Connection

    • A pump; Safety group • A 3-way manual valve. The safety group of the water tank must be approved by ACV and This valve can be motorised calibrated to 7 bar; the discharge from the group's valve must be if required;...
  • Page 10: Electrical Connections

    INSTALLATION ELECTRICAL CONNECTIONS Wiring diagram key Main switch Principle of supply Hot water control thermostat The boiler operates on a 230 V/50 Hz single-phase supply. You 24-hour programmer should install a control box with main switch and fuses externally to Heating control thermostat (60/90°C) the boiler to allow the boiler to be isolated from the supply for Manual reset high limit thermostat (103°C max.)
  • Page 11 INSTALLATION Wiring diagram of the boiler electrical circuit 230 V ˜ 50 Hz...
  • Page 12: Burner Characteristics

    BURNER CHARACTERISTICS DESCRIPTION OF THE BURNER Advantages • Easy to install, fitted with a safety shut-off and a new burner suspension system. This new generation of oil-fired burners meets current requirements • A special tool supplied with the burner is used for all maintenance for the performance and cleanliness of combustion gases.
  • Page 13: Burner Dimensions

    BURNER CHARACTERISTICS SETTING PARAMETERS BM R 31 BM R 51 BNE 1 BNE 2 BNE 3 Input 23.0 30.0 49.0 Electrical output Nozzle gal/h 0.50 0.75 1.25 Nozzle angle 60° 60° 60° Fuel oil flow rate Kg/h 1.94 2.53 4.13 Pump pressure 13.5...
  • Page 14: Commissioning And Maintenance

    COMMISSIONING AND MAINTENANCE FILLING THE HOT WATER AND HEATING SAFETY EQUIPMENT MAINTENANCE CIRCUITS - Check that all thermostats and safety devices are in good working order: boiler thermostat and 103°C manual reset high limit thermostat. IMPORTANT - Check the safety valves in both the heating circuit and hot water It is essential that the hot water circuit is filled before circuit.
  • Page 15 COMMISSIONING AND MAINTENANCE Fig. 18: Heating connection Fig. 19: Hot water connection...
  • Page 16: Spare Parts

    SPARE PARTS Casings BNE 1 BNE 2 BNE 3 Right side 21471384 21471385 21471386 Left side 21472384 21472385 21472386 Front panel 21473384 21573385 21473386 Rear panel 21474384 21474385 21474386 Top cover 21475384 21475384 21475386 Unequipped control panel 21477384 21477384 21477376...
  • Page 17: Service Record

    SERVICE RECORD DETAILS OF THE INSTALLATION Installation date: Model: % CO Serial number: (max. load) Flue gas T°: Heating system pressure setting: Efficiency: Name and signature: Fuel oil pressure: SERVICE NOTES Installation date: Comments: % CO (max. load) Flue gas T°: Efficiency: Name and signature: Fuel oil pressure:...
  • Page 20 E-MAIL: polska.info@acv-world.com E-MAIL: sales@triangletube.com E-MAIL: ceskarepublika.info@acv-world.com PORTUGAL DEUTSCHLAND BOILERNOX LDA ACV WÄRMETECHNIK GMBH & CO KG RUA OUTEIRO DO POMAR GEWERBEGEBIET GARTENSTRASSE CASAL DO CEGO, FRACÇÃO C, D-08132 MÜLSEN OT ST. JACOB - DEUTSCHLAND PAVILHÃO 3 - MARRAZES TEL.:+49 37601 311 30...